10.7. Airtight test and evacuation

10.7. Airtight test and evacuation

1Airtight test

Airtight test should be made by pressurizing nitrogen gas to 3.0 MPa. For the test method, refer to the following figure. (Make a test with the ball valve closed. Be also sure to pressurize both liquid pipe and gas pipe.)

The test result can be judged good if the pressure has not bee reduced after leaving for about one day after completion of nitrogen gas pressuriza- tion.

A Nitrogen gas

BTo indoor unit

CSystem analyzer

D Lo knob

 

E Hi knob

 

F Ball valve

A

G Liquid pipe

C

H Gas pipe

 

IOutdoor unit

JService port

B

C

LO

HI

D Manual backgroundManual backgroundManual background E

F

G

H

I

J

2Evacuation

Evacuation should be made from the service port provided on the outdoor unit’s ball valve to the vacuum pump commonly used for both liquid pipe and gas pipe. (Make evacuation from both liquid pipe and gas pipe with the ball valve closed.)

Also evacuate the oil balance pipe that connects the variable capacity and constant capacity units with the oil balance ball valves of both units shut. Evacuate from the service port of the variable capacity unit ball valve with a vacuum pump.

*Never perform air purging using refrigerant.

 

 

D

N

P

 

 

E

 

D

 

 

F

 

 

LO A

HI

 

 

 

B

C

G

 

G

 

 

 

I

 

 

H

 

 

 

 

 

J M

O

K

L

ENGLISH

ASystem analyzer

BLo Knob

CHi Knob

DBall valve

ELiquid pipe

FGas pipe

GService port

HThree-way joint

IValve

JValve

KFreon 22 cylinder

LScale

Use a graviometer. (One that can measure down to 0.1 kg.) If you are unable to prepare such a high-precision gravimeter, you may use a charge cylinder.

MVacuum pump

NConstant capacity unit side

OOil balance pipe

PVariable capacity unit side

Note:

Always add an appropriate amount of refrigerant. (For the refrigerant additional charge, see pages 13 to 14.) Too much or too little refrigerant will cause trouble.

Note that it is not possible to determine if a correct amount is being used with the accumulator level (AL).

Manual background Warning:

When installing and moving the air conditioner to another site, do not charge the it with a refrigerant different from the refrigerant (R22) specified on the unit.

- If a different refrigerant or air is mixed with the original refrigerant, the refrigerant cycle may malfunction and the unit may be damaged.