12.3. How to cope with test run abnormality

WT02979X01.pdf

1 A 4-digit check code is displayed on remote controller display panel if unit is stopped due to an abnormality. Check to see causes of that

abnormality.

1. Indoor unit

Check code

Abnormality

Check code

Abnormality

2500

Water leakage abnormality

6603

Transmission error (Transmission route BUSY)

2502

Drain pump error

6606

Transmission and reception error

2503

Drain sensor error, Float switch on

 

(Communication trouble with transmission processor)

5101

Air inlet sensor error

6607

Transmission and reception error (No ACK error)

5102

Piping sensor error

6608

Transmission and reception error (No responsive frame

5103

Piping sensor error in the gas side

 

error)

6600

Duplicated unit address setting

7101

Capacity code error

6602

Transmission error

7111

Remote controller sensor error

 

(Transmission processor hardware error)

 

 

2.Outdoor unit

a. Variable capacity unit

 

 

 

 

 

 

Check code

Abnormality

Check code

Abnormality

 

ENGLISH

0403

Serial transmission malfunction

5105

Piping temperature sensor error (TH5)

 

 

 

1102

Discharge temperature abnormality

5106

Outdoor temperature sensor error (TH6)

 

 

1111

Low pressure saturated temperature abnormality

5107

Subcool coil liquid outlet temperature sensor error (TH7)

 

 

 

(Detected by saturated temperature sensor)

 

 

 

 

1112

Low pressure saturated temperature abnormality

5108

Subcool coil bypass outlet temperature sensor error

 

 

 

(Detected by liquid level detecting temperature sensor)

 

(TH8)

 

 

 

 

 

1113

Low pressure saturated temperature abnormality

5109

Sub cool coil bypass inlet temperature sensor error (TH9)

 

 

 

(Detected by liquid level detecting temperature sensor)

5110

Inverter cooling plate temperature sensor error (THHS)

 

 

1301

Low pressure abnormality

5112

Gas pipe sensor error (TH10a)

 

 

1302

High pressure abnormality

5113

Gas pipe sensor error (TH10b)

 

 

1500

Excessive refrigerant replenishment

5201

High-pressure sensor (HPS) error

 

 

1501

Lacked refrigerant abnormality

5301

IDC sensor circuit error

 

 

1505

Low pressure abnormality

6600

Duplicated unit address setting

 

 

4103

Reverse phase

6602

Transmission error (Transmission processor hardware

 

 

4108

Overload protection (Comp overcurrent)

 

error)

 

 

4115

Power supply simultaneous signal abnormality

6603

Transmission error (Transmission route BUSY)

 

 

4116

Fan speed abnormality (motor abnormality)

6606

Transmission and reception error

 

 

4200

VDC detection circuit error

 

(Communication trouble with transmission processor)

 

 

4210

Overcurrent interruption

6607

Transmission and reception error (No ACK error)

 

 

4220

Inverter bus line voltage low

6608

Transmission and reception error (No responsive frame

 

 

4230

Overheat protection of radiator panel

 

error)

 

 

4240

Overcurrent protection

7100

Total capacity error

 

 

4260

Cooling fan abnormality

7101

Capacity code error

 

 

5101

Discharge temperature sensor error (TH1)

7102

Connecting unit number error

 

 

5102

Low pressure saturated temperature error (TH2)

7105

Address set error

 

 

5103

Liquid surface detecting temperature sensor error (TH3)

7109

Incorrect connection

 

 

5104

Liquid surface detecting temperature sensor error (TH4)

7130

Incorrect setup

 

 

b. Constand capacity unit

 

 

 

 

 

 

 

 

 

Check code

Abnormality

Check code

Abnormality

 

 

1102

Discharge temperature abnormality

5106

Outdoor temperature sensor error (TH6)

 

 

1112

Low pressure saturated temperature abnormality

5107

Subcool coil liquid outlet temperature sensor error (TH7)

 

 

 

(Detected by liquid level detecting temperature sensor)

5108

Subcool coil bypass outlet temperature sensor error

 

 

1113

Low pressure saturated temperature abnormality

 

(TH8)

 

 

 

(Detected by liquid level detecting temperature sensor)

5109

Sub cool coil bypass inlet temperature sensor error (TH9)

 

 

1302

High pressure abnormality

5112

Gas pipe sensor error (TH10a)

 

 

1500

Excessive refrigerant replenishment

5113

Gas pipe sensor error (TH10b)

 

 

1505

Low pressure abnormality

6600

Duplicated unit address setting

 

 

1559

Faulty oil balance circuit

6602

Transmission error (Transmission processor hardware

 

 

4103

Reverse phase error

 

error)

 

 

4106

Power failure error

6603

Transmission error (Transmission route BUSY)

 

 

4108

Overload protection (Comp overcurrent)

6606

Transmission and reception error

 

 

4115

Power supply simultaneous signal abnormality

 

(Communication trouble with transmission processor)

 

 

5101

Discharge temperature sensor error (TH1)

6607

Transmission and reception error (No ACK error)

 

 

5103

Liquid surface detecting temperature sensor error (TH3)

6608

Transmission and reception error (No responsive frame

 

 

5104

Liquid surface detecting temperature sensor error (TH4)

 

error)

 

 

5105

Piping temperature sensor error (TH5)

 

 

 

 

35