Displaying the service LED

Service LED (LD1)

Error code display

Alternate display of error generating address and error code

Example At outdoor unit address 51, abnormal discharge temperature (Code 1102)

Flag display

Example SV1 ON under only compressor 1 operated

ABCDEFGH

A Flag 1

E Flag 5

B Flag 2

F Flag 6

C Flag 3

G Flag 7

D Flag 4

H Flag 8

12.4. Coping with remote controller abnormality

ENGLISH

ON/OFF –

CENTRALLY CONTROLLED

1Hr.

CHECK

ON OFF

˚C

CLOCK

 

FILTER

 

˚C

 

 

CHECK MODE

STAND BY

INDOOR UNIT

ERROR CODE

NOT AVAILABLE

TEST RUN

DEFROST

ADDRESS NO

OAUNITADDRESSNO

 

 

CLOCKON OFF

 

 

 

FILTER

 

 

CHECK

TEMP.

TIMER SET

TEST RUN

REMOTE CONTROLLER

 

 

PAR-F25MA

 

 

A

ADisplay: Appears when current is carried

 

Phenomenon

 

Cause

 

How to cope with abnormality

 

Unit does not operate and

(1)

Outdoor unit power was not turned on.

(a) Check voltage between remote controller terminals.

 

display stays off even after

(2)

Transmission or remote controller cable

(i)

Remote controller fails when voltage is 17 to 30 V.

 

pressing remote controller

 

was shorted or connection failure.

(ii) If there is no voltage

 

ON switch.

(3)

Power cable contact failure

Check the number of remote controllers and indoor units con-

1

(Current-carrying indicator

(4)

Remote controller was erroneously con-

 

nected

 

does not light up)

 

nected to unit remote controller termi-

Remove wire from transmission cable terminal block (TB3) on

 

 

 

nal block.

 

outdoor unit, and check voltage between terminals.

 

 

(5)

Too many remote controllers or indoor

 

If voltage is 17 to 30 V, check (2) and (4) at left.

 

 

 

units were connected.

 

If there is no voltage, check (1) and (3) at left.

 

“HO” indicator does not dis-

(1)

No transmission cable was connected

• Check all items at left.

 

appear. Unit does not oper-

 

to transmission cable terminal block on

 

 

 

ate even if the switch is

 

the indoor unit.

 

 

2

pressed.

(2)

Outdoor unit address was erroneously

 

 

 

 

 

set

 

 

 

 

(3)

Indoor unit address was erroneously

 

 

 

 

 

set.

 

 

 

Display comes on once but

(1)

Indoor unit power was not turned on.

• Check item at left.

3

disappears immediately after

 

 

 

 

 

a press of the switch.

 

 

 

 

37

Page 37
Image 37
Mitsubishi Electronics PUHY-YMC installation manual Coping with remote controller abnormality