ENGLISH

10.4. Oil balance pipe connection method

Oil balance piping can be took out from the front, bottom or side of the unit (left side for the variable capacity unit, right side for the constant capacity unit).

Connect piping and operate valves exactly as described below. (for details, see item 10.3.)

1 After connecting oil balance pipe, be sure to evacuate using the service port of the variable capacity unit side valve.

2 After evacuating, be sure to fully open each valve stem. If you operate with the valve closed, a shortage of oil in the compressor may occur due to lack of oil flow between units, which could result in damage to the compressor.

3 After completing work, shut the cap of the service port and handle section tightly so that gas leaking does not occur.

Warning:

Failure to connect the oil balance pipe will result in the compressor being damaged.

Provide 10 mm of clearance between the variable capacity and constant capacity units. Position the variable capacity unit so that its front is facing on the right side and the constant capacity unit so that its front is facing on the left. Connect the oil balance pipe for the optional CMC-30A according to the following procedure.

1 Open the knock-out holes of the left side panel for the variable capacity unit, and the right side panel for the constant capacity unit.

2 After installing the units, flare-connect the piping included with the unit (ø 12.7).

3 Block the clearance between units with the 2 seals included with the constant capacity unit.

10 mm (clearance between units)

Right side panel

Left side panel

(Constant capacity unit)

(Variable capacity unit)

Control box

Compressor

Ball valve (oil balance) ø 12.7 (flare)

Oil balance pipe 1 (optional)

Seal material (2 pieces, included)

Through holes for oil balance pipe and transmission cables

Control box

Oil balance pipe 2

(optional)Ball valve (oil balance) ø 12.7 (flare)

Flare connection (3 places)

Tightening torque is 55 N·m (550 kg·cm) Open and close using a double spanner. Apply a coat of refrigerating machine oil on both sides of the flare contact surface.

If the oil balance piping for the constant capacity unit from the front of the unit is took out, bend the piping as shown in the figure below. (When doing so, be careful not to the piping doesn’t touch the compressor or other parts.)

Front panel

 

 

Knock-out holes for

 

Ball valve (oil balance)

Control box

ø 12.7 (flare)

taking out oil balance pipe

Compressor

 

from front surface

 

 

 

 

Oil balance pipe (Bend piping at the site.)

(Constant capacity unit)

18

Page 18
Image 18
Mitsubishi Electronics PUHY-YMC installation manual Oil balance pipe connection method, Constant capacity unit