Mitsubishi Electronics PUHY-YMC Wiring transmission cables, English, Types of control cables

Models: PUHY-YMC

1 103
Download 103 pages 62.79 Kb
Page 27
Image 27
11.3. Wiring transmission cables

11.3. Wiring transmission cables

Wiring method, address setting method and permissible wiring length differ according to and whether or not you are using transmission booster. Check permissible wiring length before wiring.

A may be required depending on the number of indoor units. Item 4 “Wiring examples” gives typical wiring examples (a-c).

a.System using remote controller (1 outdoor unit)

b.System using remote controller (system operated as a group among multiple refrigerant systems)

c.System using power supply extension unit for transmission booster (combination of systems a-b)

1Connecting a transmission booster

A transmission booster (RP) is required when the number of connected indoor unit models in a cooling system exceeds the number of models specified in the chart below.

* The maximum number of units that can be controlled is determined by the indoor unit model, the type of remote controller and their capabilities.

 

Remote controller type

Remote controller PAR-F 25MA

(*1)

 

 

 

Capability of the

Number of connected indoor units that can be

Prior to Ver. E

After Ver. F

connected indoor units

connected without a RP.

 

 

 

200 or lower

16 (32)

20 (40)

 

200 or higher

16 (32)

16 (32)

The number of indoor units and the total number of remote controllers is displayed within the parenthesis ( ).

*1 If even one unit that is higher than 200 exists in the cooling system, the maximum capacity will be “200 or higher”.

2Name, code and possible unit connections

 

Name

Code

Possible unit connections

Outdoor unit

Variable capacity unit controller

OC

Constant capacity unit controller

OS

1 unit per 1 OC.

 

Indoor unit

Indoor unit controller

IC

2 to 32 units per 1 OC (*1).

Remote controller

Remote controller (*1)

RC

2 units maximum per group.

Other

Transmission booster unit

RP

0 to 1 unit per 1 OC (*1).

*1 A transmission booster (RP) may be required depending on the number of connected indoor unit controllers.

3Types of control cables

(1) Wiring transmission cables

Types of transmission cables Shielding wire CVVS or CPEVS

Cable diameter More than 1.25 mm2

Maximum wiring length within 200 m

(2) Remote control cables

Kind of remote control cable

2-core cable (unshielded)

Cable diameter

0.5 to 0.75 mm2

Remarks

When 10 m is exceeded, use cable with the same

specifications as (1) Transmission line wiring.

 

4Wiring examples

Typical wiring examples are shown on pages 28 to 32. (Wiring examples A ~ C)

ENGLISH

27

Page 27
Image 27
Mitsubishi Electronics PUHY-YMC Wiring transmission cables, English, Connecting a transmission booster, Wiring examples