Mitsubishi Electronics PUHY-YMC Combination with indoor units, Confirmation of parts attached

Models: PUHY-YMC

1 103
Download 103 pages 62.79 Kb
Page 5
Image 5
2. Combination with indoor units

2. Combination with indoor units

The indoor units connectable to this unit are shown below.

Outdoor unit model

Total capacity of

Quantity of connectable

 

 

 

connected indoor unit

 

Model name of connectable indoor unit

 

name

models

indoor unit

 

 

 

 

 

 

 

 

 

 

 

 

 

PUHY-600

300 to 780

 

PLFY- P32 · 40 · 50 · 63 · 80 · 100 · 125

VKM

 

PLFY- P20 · 25 · 32 · 40 · 50 · 63 · 80 · 100 · 125

VLMD

 

 

 

PUHY-650

325 to 845

 

PEFY- P20 · 25 · 32 · 40 · 50 · 63 · 80 · 100 · 125

VM

 

PDFY- P20 · 25

· 32 · 40 · 50 · 63 · 71 · 80 · 100 · 125 VM

 

 

 

 

 

3 to 32

PCFY- P40 · 63

· 100 · 125

VGM

 

 

PUHY-700

350 to 910

 

PKFY- P20 · 25

 

VAM

 

 

 

PKFY- P32 · 40

· 50

VGM

PUHY-750

375 to 975

 

PFFY- P25 · 32 · 40 · 50 · 63

VLEM

 

PFFY- P25 · 32 · 40 · 50 · 63

VLRM

 

 

 

 

 

 

 

 

 

Note:

1.The total capacity of connected indoor unit models represents the total sum of the figures expressed in the indoor model name.

2.Combinations in which the total capacity of the connected indoor units exceeds the capacity of the outdoor unit will reduce the capacity of each indoor unit below the rated capacity during simultaneous operation. Therefore, if circumstances allows, combine indoor units within the capacity of the outdoor unit

3.A transmission booster (RP) is required when the number of connected indoor unit models in a cooling system exceeds the number of models specified in the chart below.

*The maximum number of units that can be controlled is determined by the indoor unit model, the type of remote controller and their capabilities.

 

Remote controller type

Remote controller PAR-F 25MA

(*1)

 

 

 

Capability of the

Number of connected indoor units that can be

Prior to Ver. E

After Ver. F

connected indoor units

connected without a RP.

 

 

 

200 or lower

16 (32)

20 (40)

 

200 or higher

16 (32)

16 (32)

The number of indoor units and the total number of remote controllers is displayed within the parenthesis ( ).

*1 If even one unit that is higher than 200 exists in the cooling system, the maximum capacity will be “200 or higher”.

3. Confirmation of parts attached

This outdoor unit is attached with the parts below. Please check the quantity for each item.

 

Name

1 Conduit mounting plate

2 Conduit mounting plate

3 Conduit mounting plate

4 Tapping screw M4 12

 

 

ø 40

ø 33

ø 27

 

 

Shape

 

 

 

 

name

PUHN-200YMC

1

1

1

4

Model

PUHN-250YMC

 

 

 

 

 

 

 

 

 

 

Name

5 Oil balance pipe

6 Connecting pipe

7 Packing

8 Seal

 

Shape

 

 

 

 

 

 

 

 

insideø 23 outsideø 35

 

name

PUHN-200YMC

1

1

1

2

Model

PUHN-250YMC

 

 

 

 

 

 

 

 

 

 

 

 

 

*6 Connecting pipe is fixed with the unit.

ENGLISH

5

Page 5
Image 5
Mitsubishi Electronics PUHY-YMC Combination with indoor units, Confirmation of parts attached, English, After Ver. F