Mitsubishi Electronics PUHY-YMC installation manual Distributor gas connection method, English

Models: PUHY-YMC

1 103
Download 103 pages 62.79 Kb
Page 19
Image 19
10.5.Distributor (gas) connection method

10.5.Distributor (gas) connection method

Taking out piping from the front direction

(1)Remove the copper cap and rubber packing attached to the pip- ing and flange of the distributor (gas) (optional).

(2)Assemble outside the unit with the elbow (8) in the specified shape and braze. (see Fig. 1.)

For the 600 type, braze the connecting pipe (7) also.

Brazing

8Elbow

Taking out piping in the downward direction

(1)Remove the copper cap and rubber packing attached to the pip- ing and flange of the distributor (gas) (optional).

(2)Assemble outside the unit with the elbow (8), connecting pipe (7 for 600 type), or connecting pipe (6 for types other than 600) in the specified shape and braze. (see Fig. 4.)

Brazing

 

 

Brazing

8Elbow

 

 

 

 

For 600

: 7Connecting pipe

 

For other than 600

: 6Connecting pipe

8Elbow

7Connecting pipe

Fig. 4

Fig. 1

(3)Braze the connecting pipe (4) and piping assembled in step (2) to the distributor (gas) so that the connecting pipe is attached as shown in Fig. 2. For assembly procedure, see Fig. 3. When braz- ing piping, cool the brazed portion of the distributor side piping with a dampened waste cloth to prevent heating by brazing.

Flange

4Connecting pipe

Distributor (gas)

Elbow assembly

Fastening plate

Fig. 2

4Connecting pipe

Flange

Fastening plate

Distributor (gas)

Fig. 3

(4)Connect the ø 12.7 oil balance pipe to the ball valve of the vari- able capacity unit (oil balance) and constant capacity unit.

(5)Connect the ø 15.88 piping branched by the distributor (liquid) to the ball valve of the variable capacity unit (liquid side).

(6)Insert the distributor (gas) into the variable capacity unit and con- nect to the flange of the ball valve (gas side). (Use a socket wrench and socket wrench extension.) When doing so, be sure to mount the included packing between the ball valve (gas side) and flange of the distributor.

(7)Fasten the plate of the distributor (gas) to the frame of the unit with screws.

(8)Connect and braze the ø 44.45 (ø 38.1 for 600 type) gas piping (main pipe) and ø 28.58 gas pipe that connects the constant ca- pacity unit with the distributor (gas).

(3)Braze the connecting pipe (5) and connecting piping assembled in step (2) to the distributor (gas) outside the unit. For assembly procedure, see Fig. 5. When brazing piping, cool the brazed por- tion of the distributor side piping with a dampened waste cloth to prevent heating by brazing.

ENGLISH

5Connecting pile

Flange

Manual background Fastening plate

Distributor (gas)

Fig. 5

The rest of the procedure is the same as for “Running piping from front direction”.

Manual background Caution:

When brazing, cool with a waste cloth dampened with water so that the flange and ends of the distributor side piping don’t get heated.

- Part could be damaged if not cooled sufficiently.

19

Page 19
Image 19
Mitsubishi Electronics PUHY-YMC installation manual Distributor gas connection method, English