12.5. The following phenomena do not represent abnormality (emergency)

12.5. The following phenomena do not represent abnormality (emergency)

 

 

Phenomenon

Display of remote controller

Cause

 

 

Indoor unit does not the perform cool-

“Cooling (heating)” flashes

When another indoor unit is performing the heating (cooling) opera-

 

 

ing (heating) operation.

 

tion, the cooling (heating) operation is not performed.

 

 

The auto vane runs freely.

Normal display

Because of the control operation of auto vane, it may change over to

 

 

 

 

horizontal blow automatically from the downward blow in cooling in case

 

 

 

 

the downward blow operation has been continued for 1 hour. At de-

 

 

 

 

frosting in heating, hot adjusting and thermostat OFF, it automatically

 

 

 

 

changes over to horizontal blow.

 

 

Fan setting changes during heating.

Normal display

Ultra-low speed operation is commenced at thermostat OFF.

 

 

 

 

Light air automatically changes over to set value by time or piping tem-

 

 

 

 

perature at thermostat ON.

 

 

Fan stops during heating operation.

Defrost display

The fan is to stop during defrosting.

 

 

Fan does not stop while operation has

No lighting

Fan is to run for 1 minute after stopping to exhaust residual heat (only

 

 

been stopped.

 

in heating).

 

 

No setting of fan while start SW has

Heat ready

Ultra low-speed operation for 5 minutes after SW ON or until piping

 

 

been turned on.

 

temperature becomes 35°C, low speed operation for 2 minutes there-

 

 

 

 

after, and then set notch is commenced. (Hot adjust control)

 

 

Outdoor unit does not operate by turn-

Normal display

When the outdoor unit is being cooled and the refrigerant is resting,

 

ENGLISH

 

ing switch on.

 

warming up operation is performed for at least 35 minutes to warm the

 

 

 

compressor.

 

 

 

 

 

 

 

 

During this time, only the fan operates.

 

 

Indoor unit remote controller shows

“HO” flashes

System is being driven.

 

 

“HO” indicator for about two minutes

 

Operate remote controller again after “HO” disappear.

 

 

when turning ON universal power sup-

 

 

 

 

ply.

 

 

 

 

 

 

 

Drain pump does not stop while unit has

Light out

After a stop of cooling operation, unit continues to operate drain pump

 

 

been stopped.

 

for three minutes and then stops it.

 

 

Drain pump continues to operate while

 

Unit continues to operate drain pump if drainage is generated, even

 

 

unit has been stopped.

 

during a stop.

 

 

When the variable capacity unit is run-

Normal display

The fan of constant capacity unit is run automatically in order not to

 

 

ning, the fan of the constant capacity

 

accumulate the refrigerant.

 

 

unit runs even though the constant ca-

 

 

 

 

pacity unit isn’t running.

 

 