Multiquip DA700SSW, DA7000WGH manual Output Voltage Verification, Operation, Idle Control Switch ON

Models: DA700SSW DA7000WGH

1 172
Download 172 pages 43.7 Kb
Page 29
Image 29
Figure 19. Idle Control Switch (ON)

OPERATION

4.If the engine does not start within 10 seconds after the key is turned to the START position, wait for about 30 seconds and repeat the procedure as described in step 4. above.

5.When the engine starts, the oil pressure light and charge light should go out. If these lights stay on, immediately stop the engine and check the system and wiring (refer to the Engine Operation Manual).

6.Let the engine idle for five minutes with the Idle Control Switch (Figure 19) placed in the ON position.

Figure 19. Idle Control Switch (ON)

Output Voltage VerificationFigure 20. Main Circuit Breaker (ON) NOTICE

Placing the idle control switch (Figure 19) in the OFF position allows the engine to operate at a maximum speed of about 3600 RPM's.

When the idle control switch is placed in the up position (ON), the generator will run at idle speed (2200 RPM's) until a load is applied, at that time the engine speed will increase to 3600 RPM's as long as a load is being applied.

When the load is not in use, the engine speed will drop back to the idle mode after about 3 seconds.

Output Voltage Verification

1.Place main circuit breaker (Figure 20) in the ON position.

 

 

 

 

 

 

 

 

 

 

 

 

ON

 

ON

25A

 

25A

 

 

 

Figure 20. Main Circuit Breaker (ON)

2.Place GFCI circuit breaker (Figure 21) in the ON position.

Figure 21. GFCI Circuit Breaker (ON)

3.Read voltmeter on front panel of generator (Figure 22) and verify that 120 VAC is displayed. Using an external voltmeter as shown in Figure 22, verify that 120 VAC is present at the 120V twist-lock and GFCI duplex receptacles.

Figure 22. 120V GFCI/L5-30R Receptacles

Figure 21. GFCI Circuit Breaker (ON) NOTICE

When using a combination of dual receptacles, total load should not exceed the rated capacity of the generator.

DA7000 SERIES GENERATORS • OPERATION AND PARTS MANUAL — REV. #5 (01/20/11) — PAGE 29

Page 29
Image 29
Multiquip DA700SSW, DA7000WGH manual Output Voltage Verification, Operation, Idle Control Switch ON, Main Circuit Breaker ON