Multiquip DA7000WGH Operation/Shutdown, Stopping the Engine Normal Shutdown, Emergency Shutdown

Models: DA700SSW DA7000WGH

1 172
Download 172 pages 43.7 Kb
Page 30
Image 30
OPERATION/SHUTDOWN

OPERATION/SHUTDOWN

4.The CS-6369 receptacle is a dual voltage receptacle (120/240 volts). Using an external voltmeter as shown in Figure 23, verify that 120/240 VAC is present at the CS-6369 twist-lock receptacle..

Figure 23. 120/240 CS-6369 Receptacle

5.The L14-30R receptacle is a dual voltage receptacle (120/240 volts). Using an external voltmeter as shown in Figure 24, verify that 120/240 VAC is present at the L14-30R twist-lock receptacle.

Figure 24. 120/240V L14-30R Receptacle

6.Connecting of loads (power tools, lighting ect.) to the generator receptacles can now be done.

Stopping the Engine (Normal Shutdown)

1.Place main circuit breaker (Figure 25) in the OFF position.

OFF

 

OFF

 

 

 

 

 

 

25A

 

25A

 

 

 

Figure 25. Main Circuit Breaker (OFF)

2.Place GFCI circuit breakers (Figure 26) in the OFF positing.

Figure 26. GFCI Circuit Breakers (OFF)

3.Place idle control switch switch (Figure 27) in the ON position.

Figure 27. Idle Control switch (OFF)

4.Let engine run at idle with no load for 3-5 minutes.

5.Place the starter switch key (Figure 28) in the STOP position and remove the key. Place fuel cock lever in the OFF position.

Figure 28. Starter Switch (Stop Position)

6. Remove all loads from the generator.

Emergency Shutdown

1.Place starter switch key in STOP position. Remove key. Place fuel cock lever in the OFF position.

PAGE 30 — DA7000 SERIES GENERATORS• OPERATION AND PARTS MANUAL — REV. #5 (01/20/11)

Page 30
Image 30
Multiquip DA7000WGH Operation/Shutdown, Stopping the Engine Normal Shutdown, Emergency Shutdown, Main Circuit Breaker OFF