DIAGNOSTIC DISPLAY

4.Touch “Select” to enter the “Gage Data” display. When “Gage Data”is selected the PowerView will communicate with the analog gages at a fi xed rate of 38.4k Band, 8 data bits, no parity check, 1 stop bits, half duplex.

GAGE DATA

REMOVE ALL GAGES

SOFTWARE VERSION

MODBUS SETUP

FAULT CONVERSION

ADJUST BACKLIGHT

DEMO MODE ON

8.When the gage data has cleared, the display automatically returns to the “Utilities” menu. Scroll to “Software Version”.Touch “Select” to view the software version currently in the diagnostic display.

SOFTWARE

VERSION

MURPHY: X.XX

5.Use the “Arrow Buttons” to scroll through the items or touch “Menu” to return to the “Utilities” menu.

1 of x

ENGINE OIL PRESSURE

ADDRESS:20

SOFTWARE REVISION #:

ERRORS: NONE

9.Touch “Menu” to return to “Utilities”. Highlight Fault Conversion” using the “Arrows”.Touch “Select” to enter the Fault conversion menu.

GAGE DATA

REMOVE ALL GAGES

SOFTWARE VERSION

FAULT CONVERSION

6. Touch “Menu Button” to return to the “Utilities” menu.

1 of x

ENGINE OIL PRESSURE

ADDRESS:20

SOFTWARE REVISION #:

ERRORS: NONE

7.Use the “Arrows” to highlight Remove All Gages”.Touch “Select” to clear gage data from memory. It takes a moment to clear all gages.

CLEARING GAGES

PLEASE WAIT

10.Use the “Arrows” to scroll to and highlight the desired version then touch “Select”. An asterisk denotes which version is currently selected.

NOTICE

There are four (4) different methods for converting fault codes. The diagnostic display always looks for J1939 Version 4 and can be set to read the code as one of three (3) other J1939 versions if Version 4 is not being used. Most engine ECU’s use Version 4, therefore in most cases adjustment of this menu option will not be required.

Upon receiving an unrecognizable fault, change to a different J1939 Version. If the fault SPN does not change when the version is changed, the ECU generating the fault is using Fault Conversion method 4. If the SPN number does not change but is still unrecognizable, try changing to another J1939 Version not yet used and continue to check the SPN number.

J1939 VERSION 1

J1939 VERSION 2

J1939 VERSION 3

PAGE 32 — DCA85USJ2 60 HZ GENERATOR • OPERATION AND PARTS MANUAL — REV. #1 (03/22/11)

Page 32
Image 32
Multiquip DCA85usJ2 manual Touch Menu Button to return to the Utilities menu