OUTPUT TERMINAL PANEL CONNECTIONS

3Ø-480/277V UVWO Terminal Output Voltages

1.Place the voltage selector switch in the 3Ø 480/277 position as shown in Figure 25.

1Ø-240/120V UVWO Terminal Output Voltages

1.Place the voltage selector switch in the 1Ø 240/120 position as shown in Figure 27.

Figure 25. Voltage Selector Switch

3Ø-480/277V Position

2.Connect the load wires to the UVWO terminals as shown in Figure 26.

Figure 26. UVWO Terminal Lugs

3Ø-440/254V Connections

3.Turn the voltage regulator knob (Figure 22) clockwise to increase voltage output, turn counterclockwise to decrease voltage output. Use voltage regulator adjustment knob whenever fi ne tuning of the output voltage is required.

Figure 27. Voltage Selector Switch

1Ø-240/120V Position

2.Connect the load wires to the UVWO terminals as shown in Figure 28.

Figure 28. UVWO Terminal Lugs

1Ø-200/100V Connections

3.Turn the voltage regulator knob (Figure 22) clockwise to increase voltage output, turn counterclockwise to decrease voltage output. Use voltage regulator adjustment knob whenever fi ne tuning of the output voltage is required.

NOTICE

ALWAYS make sure that the connections to the UVWO terminals are secure and tight.The possibility of arcing exists, that could cause a fi re.

DCA85USJ2 60 HZ GENERATOR • OPERATION AND PARTS MANUAL — REV. #1 (03/22/11) — PAGE 45

Page 45
Image 45
Multiquip DCA85usJ2 manual 3Ø-480/277V Uvwo Terminal Output Voltages, 1Ø-240/120V Uvwo Terminal Output Voltages