Chapter 3 Example Applications
©
National Instruments Corporation 3-13 FieldPoint FP-3000 User Manual
PID ControlInstantiate a PID BlockNow that your input and output blocks are functioning, you can “close the
loop” by creating a control block and putting the loop under automatic
control. To instantiate a PID block, follow these steps:
1. Right-click on FP-3000 in the configurator.
2. Select Instantiate New Block. This causes a dialog box to appear that
lists all of the blocks supported by the FP-3000 and allows them to be
instantiated.
3. Select Proportional Integral Derivative Block from the list, then
click on the OK button.
Assign a Tag to the New Block
By default, new blocks are created without a tag. To assign a tag, follow
these steps:
1. Right-click on Proportional Integral Derivative Block, then select
Set Tag.
2. Enter the tag you choose in the dialog box. The tag can be up to
32 characters in length and should not contain the dot (“.”) character.
3. Click on OK.
Scale the PIDThe PID has a PV_SCALE for scaling its input. The PV_SCALE should
match the output scale (OUT_SCALE) of the AI block. To set the PID, enter
the following:
PV_SCALE
EU at 100% 1775
EU at 0% -273
Units Index °C
Decimal 2
The AO block takes a percentage range from the controller of 0 to 100
percent, so adjust the PID block to output that range. To set the OUT_SCALE
parameter of the PID, enter the following:
OUT_SCALE
EU at 100% 100
EU at 0% 0
Units Index %
Decimal 2