Appendix C Fieldbus Parameters
©
National Instruments Corporation C-3 FieldPoint FP-3000 User Manual
Table C-1. Error Codes
Error Code Code Description
Other 0x0001 Undefined block error condition.
Block Configuration Error 0x0002 The block has detected an error in its configuration.
This usually indicates a static parameter has been left
uninitialized.
Link Configuration Error 0x0004 The logical connection between this block and another
block is misconfigured.
Simulate Active 0x0008 F or I/O function blocks, this indicates that simulation is
enabled. For the resource block, this indicates that the
simulate jumper has been set, allowing simulation to be
enabled in other blocks.
Local Override 0x0010 The block has locally overridden the output value.
This can be the result of an interlock or faultstate.
Device Faultstate Set 0x0020 The block’s faultstate behavior is active.
Device Needs
Maintenance Soon 0x0040 The device is reporting performance degradation that
will soon require maintenance.
Input Failure/BAD PV
Status 0x0080 Either the input transducer channel has reported a
failure, or the input parameter from an upstream block
has reported a failure. For an AI block, this could be
caused by an open circuit being detected on the
FP-AI-100 input module.
Output Failure 0x0100 The output transducer channel has reported a failure. For
an AO block, this could indicate that the FP-AO-200
cannot drive the current request, perhaps due to an open
circuit.
Memory Failure 0x0200 The storage for nonvolatile and static parameters was
corrupted.
Lost Static Data 0x0400 The device was unable to restore the values of static
parameters after a restart.
Lost NV Data 0x0800 The device was unable to restore the values of
nonvolatile parameters after a restart.
Readback Check Failed 0x1000 The value read back from the output channel does not
match the value the output channel was set to.