Chapter 4 Block Reference
FieldPoint FP-3000 User Manual 4-10
©
National Instruments Corporation
LimitTable 4-4 describes the Limit subfield values.
MODE_BLK Parameter and Mode HandlingThe block’s mode behavior is controlled with the MODE_BLK parameter.
The MODE_BLK parameter contains four fields that allow the current mode
of the block to be read and the desired mode for the block to be written. The
four fields are Target mode, Actual mode, Permitted mode, and
Normal mode.
Target ModeThe desired mode of execution for the block. An operator or process
engineer normally writes this to put the block in the desired mode of
operation.
Table 4-4. Limit Values
Valu e Meaning
None The value is not limited.
Low The value is at a lower limit. This can be caused by
a transducer limitation or setpoint limits.
High The value is at a high limit. This can be caused by
a transducer limitation or setpoint limits.
Constant The value is at a fixed value and cannot move. This
can be caused by the block supplying the value
being in manual mode.
Table 4-5. Target Modes
Desired Mode Bit Set in Target Mode
Out of Service Out of Service, and optionally any other
valid target mode
Manual Manual
Automatic Automatic
Cascade Cascade and Automatic