Appendix B Troubleshooting
FieldPoint FP-3000 User Manual B-2
©
National Instruments Corporation
TableB-1 describes common Fieldbus communication problems and
possible solutions.
Table B-1. Fieldbus Communication Problems
Problem Solutions
FP-3000 is not visible on the
Fieldbus from a host configurator • Is the power LED on? If not, check your power supply and
DC power wiring to the FP-3000.
• Is the Fieldbus network light on? If not, your Fieldbus
wiring is probably bad.
• Check the switches on the back of the FP-3000. Make sure
the Reset switch is not On. Refer to Appendix A,
Configuring the FP-3000, to view a diagram of the
configuration switches.
• Is your Fieldbus host probing the network address of the
FP-3000? If not, the FP-3000 will not be able to get on the
network. Check your host documentation for how to make
the host probe all network addresses. For NI-FBUS, use the
Interface Config program, select Advanced settings for
the interface port, and set Num of unpolled nodes to 0,
then restart NI-FBUS.
FP-3000 NETWORK LED is
red (steady or flashing) Check your Fieldbus wiring for short circuits or other electrical
problems.
FP-3000 is visible on the
Fieldbus from a host, but no
blocks show up
If you are running NI-FBUS Configurator, and this is your first
startup of FP-3000, wait a couple of minutes for the
Configurator to complete setting the address and device tag of
the FP-3000. When the process is complete, the blocks will
show up.
Otherwise, FP-3000 might be stuck at a default network
address with no tag. Consult your host documentation on how
to set the address and device tag.
All the blocks and configuration
information are lost on a power
cycle
Make sure the Reset switch at the back of the FP-3000 is set
correctly. Refer to AppendixA, Configuring the FP-3000, for
details.
FP-3000 does not execute the
communication schedule when it
becomes LAS
You must download a schedule to the FP-3000. If you are using
NI-FBUS Configurator, make sure FP-3000 is in the list of
devices to receive a schedule.