Appendix B Troubleshooting
FieldPoint FP-3000 User Manual B-6
©
National Instruments Corporation
Cannot access or view the
parameters added by National
Instruments
Make sure that the Device Descriptions are installed in the
correct location. Refer to the section Install the Device
Description File in Chapter 2, Installation and Configuration,
if you are using NI-FBUS.
Cannot set the values of certain
parameters Most configuration parameters of function blocks can be
changed only when the block is in OOS mode. Set the mode to
OOS and then change the configuration parameters.
Table B-4. Resource Block Configuration Problems
Problem Action
Cannot bring Resource Block
into Auto mode Make sure the Reset switch is disabled. You cannot bring the
Resource Block into Auto with the Reset switch On (this
prevents you from losing your entire configuration if you
inadvertently leave the Reset switch On).
Cannot set the WRITE_LOCK
parameter. Make sure the Write Lock switch is On. Changing
WRITE_LOCK is enabled only when the Write Lock switch is
On. If you want to disallow configuration writes to the device,
set the Write Lock switch to On, then write Locked to this
parameter.
Table B-3. Generic Software Configuration Problems (Continued)
Problem Solutions