Appendix C Fieldbus Parameters
©
National Instruments Corporation C-17 FieldPoint FP-3000 User Manual
RCAS_OUTThe back calculation output used by the host when establishing a Remote
cascade loop.
RESETThe time constant for the integral component of the PID block. It is
measured in seconds per repeat.
RESTARTAllows the user to restart the device remotely. TableC-12 lists restart
values.
Caution Using Restart to Default causes all your configured parameters in the
FP-3000 to revert to their factory default settings.
ROUT_INThe cascade input set by a remote host. This is propagated to the output of
the block when it is in ROut mode. If the block is in ROut mode and this
parameter is not updated in SHED_ROUT time (a parameter in the resource
block), the block enters mode shedding. Mode shedding allows the block to
degrade from ROut mode into some higher priority mode. For more
information on mode shedding, refer to Appendix D, Advanced Function
Block Behavior.
ROUT_OUTThis is the back calculation output used by the host when trying to establish
a remote output loop. While the loop is being established, it is the current
value of the output channel and can be used by the host to initialize for
smooth transfer of control.
Table C-12. Restart Values
Valu e Behavior
Restart
Resource Restarts the device.
Restart to
Defaults Restarts the device, restoring all parameter values to
default values.
Restart
Processor Restarts the device as if the power was cycled.