1.1.3 Control Settings

Select “Controls” in the settings menu, then press the <Set> key.

The control settings appear. The settings available depend on the selected signal source and the control type. The opposite display shows the maximum number of settings available.

DESCRIPTION OF THE SETTINGS

SignalSource

Selecting the signal source.

 

Factory setting: Analog

 

Options:

Analog

 

 

Modbus

Hum.Control:

Selecting the control type.

 

Factory setting: External

 

Options: External (external continuous controller)

 

24VOn/Off (external On/Off humidistat)

 

Int. (P) (Internal P controller)

 

Int. (PI) (Internal PI controller)

Controlsign.

Selecting the control signal.

 

NOTE: This setting is available only if control type

 

“External”, “Int. (P)” or “Int. (PI)” is selected.

 

Factory setting: 0–10V

 

Options: 0–5V, 1–5V, 0–10V, 2–10V, 0–16V, 3.2–

 

16V, 0–20mA, 4–20mA

Hum.Setpoint:

Setting the nominal humidity value inn %rh.

 

NOTE: This setting is available only if the internal P

 

or PI controller is activated.

 

Factory setting: 50 %rH

 

Setting range: 20...99 %rH

P-Band:

Setting the proportional range inn % for the internal

 

P/PI conntroller.

 

 

NOTE: This setting is available only if the internal P

 

or PI controller is activated.

 

Factory setting: 18 %

 

Setting range:

1...100 %

Integr.-Time:

Setting the integral time in minutes for the internal

 

PI controller.

 

 

NOTE: This setting is available only if the internal P

 

or PI controller is activated.

 

Factory setting: 18 Minutes

 

Setting range:

1...60 Minutes