Nortec MH Series Setting the capacity limitation, Factory setting 100 % Setting range 30...100 %

Models: MH Series

1 40
Download 40 pages 28.61 Kb
Page 18
Image 18
1.1.4 Setting the capacity limitation

.

1.1.4 Setting the capacity limitation

Select “Power Limit” in the settings menu, then press the <Set> key. In the upcoming modification dialogue set the desired capacity limitation in % of the maximum capacity of the humidifier.

Factory setting: 100 %

Setting range: 30...100 %

1.1.5 Configuring the supply pipe flushing

Select “Inlet Flush” in the settings menu, then press the <Set> key.

Used to configure the unit to flush supply lines even if there is no demand signal. You can;

-enable / disable inlet flush

-set length of flush

-set time between flushes

DESCRIPTION OF THE SETTINGS

Inlet Flush

Enable or disable the supply pipe flushing.

 

Factory setting:

On

 

Options:

On (enable)

 

 

Off (disable)

 

 

Drain Time

Setting the flushing time in seconds.

 

Factory setting:

60s

 

Setting range:

5...600s

 

 

Periodic Int

Setting the time without demand after which

 

the supply pipe should be flushed.

 

Factory setting:

12.0 h

 

Setting range:

0.5 ... 24.0 h

 

 

 

10-10

Page 14 2008-12-03

Page 18
Image 18
Nortec MH Series Setting the capacity limitation, Factory setting 100 % Setting range 30...100 %, Options, 10-10