1.2RESETTING THE MAINTENANCE INDICATION
After completing maintenance work, the maintenance indication (yellow LED lights) must be reset on the models MHTC Flow, MHB Reflow, MHTC Reflow.
Note: If the maintenance indication is not reset within 168 hours a fault is triggered and the unit stops operation.
Select the maintenance menu:
Path: Main menu > User > Password entry: 8808 > Maintenance
Select “Module A”, then press the <Set> key.
Select "Stage Reset”, then press the <Set> key.
The reset dialogue shows up in the display. Press the <Yes> key to reset the maintenance hours of the unit.
Note: Press the <Esc> or <No> key if you wish to abort the reset procedure.
To return to the standard operating display press the <Esc> key several times.
10-20
Page 25