Nortec MH Series installation manual Unit Faults, 10-30, Page

Models: MH Series

1 40
Download 40 pages 28.61 Kb
Page 34
Image 34
1.2.2 Unit Faults

1.2.2 Unit Faults

 

Warning

 

Error

LED

Display

LED

Display

External

safety chain is

 

 

open

 

 

 

Red

 

 

--

and

 

 

 

green

 

 

 

flash

 

 

 

 

 

 

 

Error level sensor

Error level sensor

Red

 

Red

 

flashes

 

lights

 

 

 

 

 

Maximum filling time

Maximum filling time

exceeded (30 minutes)

exceeded (more than 4

 

 

hours)

Red

 

Red

 

flashes

 

lights

 

 

 

 

Note: This error

 

 

 

message is reset

 

 

 

automatically as

 

 

 

soon as the water

 

 

 

supply functions

 

 

 

again.

 

 

 

 

 

 

 

 

 

 

 

 

10-30

Page 30 2008-12-03

Cause

Air proving interlock open.

Air flow monitor triggered

Safety humidistat triggered.

The level sensor is blocked or defective (broken or short- circuited).

Water supply blocked/shut-off valve closed/water pressure too low. Water treatment unit (fully demineralised water) is regenerating.

Inlet valve blocked or defective.

Drain valve open, blocked in open position or not electrically connected. Drain valve is open unless powered

Leakage in the water drain system.

Remedy

If applicable, check/turn on fan.

Check fan/filter of the fan system.

Wait, if applicable, check safety humidistat

Check/clean or replace level sensor. Check level sensor with ohmmeter: If no water is in the tub, the circuit of the level sensor must be closed. If the water in the tub is

on maximum level sensor must be open.

Check water supply (filter, pipes, etc.), Check/open shut- off valve, Check water pressure.

Check strainer in the inlet valve, clean if necessary. Replace inlet valve.

Check/replace drain valve, connect drain valve.

Check/seal water drain system.

Page 34
Image 34
Nortec MH Series installation manual Unit Faults, 10-30, Page