1.3RESETTING THE HOURS METER OF THE UV LAMP
After replacing the UV lamp (option) the hours meter of the UV lamp must be reset. Note: If the hours meter of the UV lamp is not reset within 168 hours the UV maintenance warning an error message is triggered.
Select the maintenance menu:
Path: Main menu > User > Password entry: 8808 > Maintenance
Select “Module A”, then press the <Set> key.
Select "UV lamp Rst”, then press the <Set> key.
The reset dialogue shows up in the display.
Press the <Yes> key to reset the hours meter of the UV lamp.
Note: Press the <Esc> or <No> key if you wish to abort the reset procedure.
To return to the standard operating display press the <Esc> key several times.