Warning

 

Error

LED

Display

LED

Display

Maintenance due

Maintenance not performed

 

 

and/or maintenance

 

 

indication not reset

 

 

 

 

Red

 

red and

 

flashes

 

yellow

 

and

 

lights

 

yellow

 

 

 

lights

 

 

 

 

 

 

 

 

 

 

 

Maximum lifespan of the

Maximum lifespan of the

UV lamp reached

UV lamp reached

 

 

 

 

red

 

red and

 

flashes

 

yellow

 

and

 

light

 

yellow

 

 

 

lights

 

 

 

 

 

 

 

No signal from humidity

No signal from humidity

sensor

sensor

 

 

 

 

Red

 

Red

 

flashes

 

lights

 

 

 

 

 

10-30

Page 32 2008-12-03

Cause

Maintenance due.

Maintenance not performed and/or maintenance indication not reset within 168 h (1 week).

Maximum lifespan of the UV lamp reached.

UV lamp not replaced or hours counter of the UV lamp not reset after replacement of the UV lamp. Unit switches off after 168 hours.

Wrong UV lamp installed.

Sensor cable not connected or sensor cable interrupted.

Humidity sensor defective.

Remedy

Perform maintenance according to section 10-40 of the installation and operating instructions

for the Nortec MH. Then, reset the maintenance indication.

Perform maintenance according to section 10-40 of the installation and operating instructions

for the Nortec MH. Then, reset the maintenance indication.

Replace UV lamp and clean glass tube

Replace UV lamp and clean glass

tube (see 1.4.2 in section 10-40),

then reset hours counter of the UV lamp.

Install correct UV lamp.

Connect/replace sensor cable.

Replace humidity sensor.