1.2Modbus Settings

Select the Modbuus menu: Path: Main menu >

User > Password entry: 8808 > Modbus

The settings for the Modbuus appear.

Description of Modbus Settings

Modbus Add.:Setting the modbus address of the Nortec MH. Factory setting: 1

Setting range: 1...247

Parity:

Selecting the parity bit for the data

 

transmission.

 

Factory setting: None.

 

Options: None1, None2, Odd, Even

 

 

Timeout:

Setting the time out time for the data

 

transmission.

 

Factory setting: 5

 

Seconds Setting range: 1...600 Seconds

10-10

Page 21 2008-12-03

Page 25
Image 25