2.2SWITCHING THE CONTROL UNIT ON AND OFF

2.2SWITCHING THE CONTROL UNIT ON AND OFF

NOTE: For putting the unit into operation and taking the unit out of operation please follow the procedures described in the installation and operating instructions for the Nortec MH.

Switching the MH control unit on

The control carries out a system test, during which all the LEDs light up and the opposite display is shown. If a failure occurs on the system test, a corresponding error message is shown in the display.

After the system test the control is in normal operation mode. The display shows the standard operating display. Note: The contents of the standard operating display depends on the type (MHTC Flow, MHTC Reflow), the actual operating status and on the configuration of the Nortec MH and can differ from the opposite display.

Switching the MH control unit off

The display goes out. On models MHB Reflow and MHTC Reflow the drain valve opens and the water tub empties.

Note: The different hygiene functions (regular draining, flushing of the supply line, etc.) remain active also in times without humidification / cooling demand, the control unit should only be switched off for maintenance or, troubleshooting, or to disable completely operation (as in seasonal shutdown).

2.3REMOTE OPERATING AND FAULT INDICATION

If your control is equipped with a remote indication board (accessory) the following operating status are shown remotely:

Activated remote

When?

Display on Unit

indication relay

 

 

H1

“Error”

A fault is present, further

Red LED lights. An error

 

 

operation is not possible

message is shown in the

 

 

 

display

H2

“Service”

Maintenance or UV lamp

Yellow LED lights. The

 

 

(option) replacement is

service warning message

 

 

due. The unit remains

is shown in the display

 

 

operational for a certain

 

 

 

time

 

H3

“Humidification”

Unit is humidifying

Green LED lights

H4

“Unit on”

Unit ready for operation

Unit switch lights