Nortel Networks 411-2021-111 manual Power and Grounding Requirements

Models: 411-2021-111

1 98
Download 98 pages 40.1 Kb
Page 71
Image 71

Power and Grounding Requirements 5-3

Table 5-1

Metrocell DC Power performance requirements

Description

 

Requirements

 

 

 

 

 

 

 

 

Maximum

 

Nominal

 

Minimum

 

 

 

 

 

 

Module or unit level operating voltage range

29.00 Vdc

 

27.00 Vdc

 

21.00 Vdc

 

 

 

 

 

 

Metro RF Frame current draw per feed (A or B) with all PAs

75 Adc

 

 

 

 

transmitting at full RF output power

 

 

 

 

 

 

 

 

 

 

 

Metro RF Frame power distribution voltage drop (from the

0.65 Vdc

 

 

 

 

feed input at the RIP to any module)

 

 

 

 

 

 

 

 

 

 

 

Metro RF Frame power distribution resistance (from the

40

 

 

 

 

feed input at the RIP to any module)

MOhms

 

 

 

 

 

 

 

 

 

 

Metro RF Frame operating voltage range (measured at the

29.00 Vdc

 

27.00 Vdc

 

21.60 Vdc

RIP power feed input)

 

 

 

 

 

 

 

 

 

 

 

Metro RF Frame minimum voltage to guarantee maximum

 

 

 

 

26.20 Vdc

PA RF power is available (measured at the RIP power feed

 

 

 

 

 

input)

 

 

 

 

 

 

 

 

 

 

 

Power Plant normal operating "Float" voltage range

27.60 Vdc

 

27.25 Vdc

 

27.00 Vdc

 

 

 

 

 

 

Power Plant "Equalize" voltage (one to two days)

29.00 Vdc

 

 

 

 

 

 

 

 

 

 

Power Plant voltage drop

0.25 Vdc

 

 

 

 

 

 

 

 

 

 

Maximum power feed length (measured from Metro RF

 

 

 

 

 

Frame RIP to Power Plant breaker

 

 

 

 

 

#2/0 AWG or Welding Copper Wire

60 feet

 

 

 

 

#1/0 AWG or Welding Copper Wire

47 feet

 

 

 

 

 

 

 

 

 

 

Absolute maximum voltage (no damage, non-operational,

30.50 Vdc

 

 

 

 

applied continuously)

 

 

 

 

 

 

 

 

 

 

 

Transient voltage immunity (Metro RF Frame modules) for

40 Vdc

 

 

 

 

300 s

 

 

 

 

 

 

 

 

 

 

 

Noise from battery (system and module immunity)

 

 

 

 

 

into 600 Ohms

56 dBmC

 

 

 

 

from 10 kHz to 20 MHz in 3 kHz BW into 50 Ohms

100 mV

 

 

 

 

 

(rms)

 

 

 

 

from dc to 100 MHz into Hi-Z

250 mV

 

 

 

 

 

(p-p)

 

 

 

 

 

 

 

 

 

 

Noise to battery (system and module emissions)

 

 

 

 

 

from 300 Hz to 10 kHz (where Ip is the steady state

9+10logIp

 

 

 

 

dc current draw)

dBmC

 

 

 

 

from 10 kHz to 1 MHz

Ip**0.5 mV

 

 

 

 

 

(rms)

 

 

 

 

Broadband noise

250 mV

 

 

 

 

 

(p-p)

 

 

 

 

 

 

 

 

 

 

Battery step (system and module immunity) within nominal

±3 Vdc

 

 

 

 

operating range with 1 V/ms maximum rate of change)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DMS-MTX DualMode Metrocell Cell Site Description

Page 71
Image 71
Nortel Networks 411-2021-111 manual Power and Grounding Requirements