5.2Agency Approvals
AGENCY | MODEL | PROTECTION METHOD | AREA CLASSIFICATION | |
|
|
|
|
|
FM & CSA | Intrinsically Safe | Class I, Div. 1: | ||
|
| Groups A, B, C, & D | ||
|
| Class II, Div. 1: | ||
|
| Groups E, F, & G | ||
|
|
| Class III, IP66 TYPE 4X, T4 | |
|
|
| FISCO |
|
|
| Explosion Proof ➀ | Class I, Div. 1 | |
|
|
| Groups B, C, & D | |
|
|
| Class II, Div. 1 | |
|
|
| Groups E, F, & G | |
|
|
| Class III, IP66 Type 4X T5 at 80° C |
|
| Class I, Div. 2 | |||
|
|
| Groups A, B, C, & D | |
|
|
| Class II, Div. 2 | |
|
|
| Groups E, F, & G ➁ | |
|
|
| Class III, IP66 Type 4X T5 at 80° C |
|
ATEX | Flame Proof | II 1/2 G EExd IIC T6 | ||
|
|
|
| |
|
|
|
| |
|
|
|
| |
| Intrinsically Safe ➂ | II 1 G EEx ia IIC T4 | ||
|
|
| FISCO | |
|
|
|
|
|
|
|
|
|
|
➀ M20 conduit connections not CSA approved explosion proof ➁ FM approval Class II, Div. 2 Groups F & G only
➂ Materials marked as category 1 equipment and used in hazardous areas requiring this category, shall be installed in such a way that, even in the event of rare incidents, the aluminum enclosure cannot be an ignition source due to impact or friction
5.2.1Agency Specifications – Explosion Proof Installation
Factory Sealed: This product has been approved by Factory Mutual Research (FM) and Canadian Standards Association (CSA) as a Factory Sealed device.
NOTE: Factory Sealed: No Explosion Proof conduit fitting (EY seal) is required within 18" of the transmitter. However, an Explosion Proof conduit fitting (EY seal) is required between the haz- ardous and safe areas.
Caution: Grounding (+) will cause faulty operation, but will not cause permanent damage.
5.2.2Agency specifications ATEX Intrinsically safe
Entity parameters Fieldbus Fisco:
Ui = 17.5V Ii=380mA Pi = 5.32W Ci = 0.705 nF Li = 3µH
| 22 |