5.1.3 FF Segment Checklist

There can be several reasons for a FOUNDATION fieldbusinstallation to be in a faulty condition. In order to assure that communication can be established, the following requirements must be met.

Device supply voltage must be higher than 9 VDC with a maximum of 32 VDC.

Total current draw of a given segment cannot exceed the rating shown on the power conditioner and/or barrier.

Two 100 , 1 µF terminators must be connected to the network—one at each end of the segment.

Cable length plus spur length must not exceed the following values:

Number of Spurs

1 Device

2 Devices

3 Devices

4 Devices

 

 

 

 

 

25–32

 

 

 

 

 

19–24

100 ft. (30 m)

 

 

 

 

 

15–18

200 ft. (60 m)

100 ft. (30 m)

 

 

 

 

 

13–14

300 ft. (90 m)

200 ft. (60 m)

100 ft. (30 m)

 

 

 

 

 

1–12

400 ft. (120 m)

300 ft. (90 m)

200 ft. (60 m)

100 ft. (30 m)

 

 

 

 

 

Pair

Shield

Twisted

Size

Length

Type

 

 

 

 

 

 

 

Single

Yes

Yes

AWG 18

(0.8 mm2)

6,200 ft. (1,900 m)

A

 

 

 

 

 

 

 

Multi

Yes

Yes

AWG 22

(0.32 mm2)

3,900 ft. (1,200 m)

B

 

 

 

 

 

 

 

Multi

No

Yes

AWG 26

(0.13 mm2)

1,300 ft. (400 m)

C

 

 

 

 

 

 

 

Multi

Yes

No

AWG 16

(1.25 mm2)

650 ft. (200 m)

D

 

 

 

 

 

 

 

The cable shield is to be hard grounded only at one point close to the DCS. In addition, the cable shield can be capacitively grounded in multiple places to improve EMC protection.

21

46-649 Jupiter Magnetostrictive Transmitter - FOUNDATION fieldbus™

Page 24
Image 24
Orion 2xx manual FF Segment Checklist, Size Length Type