DD_REV: contains the revision of the DD associated with the version of firmware in the Enhanced Jupiter transmitter. It is used by interface devices to correctly select the associated DD.
RESTART: Default and Processor selections are available. Default will reset the Jupiter to the established block configuration.
NOTE: As RESTART DEFAULT will set all configuration parameters to their default values. Devices need to be reconfigured following activation of this function
FEATURES: a list of the features available in the transmitter. The Jupiter Model 2xx features include Reports, and Soft Write Locking.
FEATURES_SEL: allows the user to turn Features on or off.
CYCLE_TYPE: identifies the block execution methods that are available.
CYCLE_SEL: allows the user to select the block execution method.
MIN_CYCLE_T: the time duration of the shortest cycle interval. It puts a lower limit on the scheduling of the resource.
NV_CYCLE_T: the minimum time interval between copies of
NOTE: After completing a large copy, allow several seconds before removing power from the Jupiter Model 2xx transmitter to ensure that all data has been saved.
FREE_SPACE: shows the amount of available memory for further configuration. The value is zero percent in a pre- configured device.
FREE_TIME: the amount of the block processing time that is free to process additional blocks.
SHED_RCAS: the time duration at which to give up com- puter writes to function block RCas locations. Shed from RCas will never happen when SHED_RCAS = 0.
SHED_ROUT: the time duration at which to give up com- puter writes to function block ROut locations. Shed from ROut will never happen when SHED_ROUT = 0.
11 |
|