OD Pipe Temperature
A78.8°F (26°C)
B91.4°F (33°C)
During above condition, when indoor heat exchanger temperature is below 41°F (5°C), the outdoor fan will stop according to outdoor piping temperature as following:
12.4 Airflow Direction
There are two types of airflow, vertical airflow (directed by horizontal vane) and horizontal airflow (directed by vertical vanes).
Control of airflow direction can be automatic (angles of direction is determined by operation mode, heat exchanger temperature and intake air temperature) and manual (angles of direction can be adjusted using remote control).
12.4.1Vertical Airflow
Operation Mode | Airflow Direction |
|
| Upper Vane Angle (°) |
|
| Lower Vane Angle (°) |
| |||||
| 1 | 2 | 3 | 4 | 5 | 1 | 2 | 3 | 4 | 5 | |||
|
|
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Auto with Heat |
| A |
|
| 25 |
|
|
|
| 17 |
|
|
| Exchanger |
| B |
|
| 55 |
|
|
|
| 37 |
|
|
| Temperature |
|
|
|
|
|
|
|
|
|
|
|
|
Heating |
| C |
|
| 25 |
|
|
|
| 17 |
|
| |
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Summer House |
|
|
| 55 |
|
|
|
| 37 |
|
| |
| Manual |
| 20 | 45 | 55 | 65 | 70 | 17 | 27 | 37 | 47 | 56 | |
Cooling | Auto |
|
|
| 45 ~ 70 |
|
|
|
| 2 ~ 39 |
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
| |
Manual |
| 20 | 25 | 50 | 55 | 70 | 2 | 7 | 17 | 27 | 39 | ||
|
| ||||||||||||
Soft Dry | Auto |
|
|
| 45 ~ 70 |
|
|
|
| 2 ~ 39 |
|
| |
Manual |
| 20 | 25 | 50 | 55 | 70 | 2 | 7 | 17 | 27 | 39 | ||
|
| ||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1.Automatic vertical airflow direction can be set using remote control; the vane swings up and down within the angles as stated above. For heating mode operation, the angle of the vane depends on the indoor heat exchanger temperature as Figure 1 below. It does not swing during fan motor stop. When the air conditioner is stopped using remote control, the vane will shift to close position.
2.Manual vertical airflow direction can be set using remote control; the angles of the vane are as stated above and the positions of the vane are as Figure 2 below. When the air conditioner is stopped using remote control, the vane will shift to close position.