12.4.2Horizontal Airflow

šThe horizontal airflow direction louvers can be adjusted manually by hand.

12.5 Quiet operation (Cooling Mode/Cooling area of Dry Mode)

šPurpose

o To provide quiet cooling operation compare to normal operation.

šControl condition

o Quiet operation start condition

ƒWhen “POWERFUL/QUIET” button at remote control is pressed twice. POWERFUL/QUIET LED illuminates.

oQuiet operation stop condition

ƒWhen one of the following conditions is satisfied, quiet operation stops:

šPOWERFUL/QUIET button is pressed again.

šStop by OFF/ON switch.

šTimer “off” activates.

šAUTO COMFORT button is pressed.

šECONAVI button is pressed.

ƒWhen quiet operation is stopped, operation is shifted to normal operation with previous setting.

ƒWhen fan speed is changed, quiet operation is shifted to quiet operation of the new fan speed.

ƒWhen operation mode is changed, quiet operation is shifted to quiet operation of the new mode.

ƒDuring quiet operation, if timer “on” activates, quiet operation maintains.

ƒAfter off, when on back, quiet operation is not memorised.

šControl contents

oFan speed is changed from normal setting to quiet setting of respective fan speed. Fan speed for quiet operation is reduced from setting fan speed.

12.6 Quiet Operation (Heating)

šPurpose

o To provide quiet heating operation compare to normal operation.

šControl condition

o Quiet operation start condition

ƒWhen “POWERFUL/QUIET” button at remote control is pressed. POWERFUL/QUIET LED illuminates.

oQuiet operation stop condition

ƒWhen one of the following conditions is satisfied, quiet operation stops:

šPOWERFUL/QUIET button is pressed again.

šStop by OFF/ON switch.

šTimer “off” activates.

šAUTO COMFORT button is pressed.

šECONAVI button is pressed.

ƒWhen quiet operation is stopped, operation is shifted to normal operation with previous setting.

ƒWhen fan speed is changed, quiet operation is shifted to quiet operation of the new fan speed.

ƒWhen operation mode is changed, quiet operation is shifted to quiet operation of the new mode, except fan mode only.

ƒDuring quiet operation, if timer “on” activates, quiet operation maintains.

ƒAfter off, when on back, quiet operation is not memorised.

šControl contents

oFan speed manual

ƒFan speed is changed from normal setting to quiet setting of respective fan speed.

ƒFan speed for quiet operation is reduced from setting fan speed.

oFan Speed Auto

ƒ Indoor FM RPM depends on pipe temp sensor of indoor heat exchanger.