Panasonic CU-XE12PKUA manual Protection Control For Heating Operation, 13.2.6Odor Cut Control

Models: CU-XE12PKUA CU-XE9PKUA CS-XE9PKUA CS-XE12PKUA

1 102
Download 102 pages 16.71 Kb
Page 47
Image 47
13.2.6Odor Cut Control

13.2.6Odor Cut Control

šTo reduce the odor released from the unit. o Start Condition

ƒAUTO FAN Speed is selected during COOL or DRY operation.

ƒDuring freeze prevention control and timer preliminary operation, this control is not applicable. o Control content

ƒDepends on compressor conditions:

1.Compressor OFF → Compressor ON.

The indoor unit fan stops temporarily and then starts to blow at minimum airflow for 30 seconds.

2.Compressor ON → Compressor OFF.

The indoor unit fan stops for 90 seconds and then blows at minimum airflow for 20 seconds.

13.3 Protection Control For Heating Operation

13.3.1Intake Air Temperature Control

Compressor will operate at limited freq., if indoor intake air temperature is 86°F (30°C) or above.

13.3.2Outdoor Air Temperature Control

šThe Max current value is regulated when the outdoor air temperature rise above 57.2°F (14°C) in order to avoid compressor overloading.

13.3.3Overload Protection Control

šThe compressor operating frequency is regulated in accordance to indoor heat exchanger temperature as shown below.

šIf the heat exchanger temperature exceeds 140°F (60°C), compressor will stop.

13.3.4Low Temperature Compressor Oil Return Control

šIn heating operation, if the outdoor temperature falls below 14°F (-10°C) when compressor starts, the compressor frequency will be regulated up to 600 seconds.

13.3.5Cold Draught Prevention Control

šWhen indoor pipe temperature is low, cold draught operation starts where indoor fan speed will be reduced.

13.3.6Deice Operation

šWhen outdoor pipe temperature and outdoor air temperature is low, deice operation start where indoor fan motor and outdoor fan motor stop and operation LED blinks.

47

Page 47
Image 47
Panasonic CU-XE12PKUA Protection Control For Heating Operation, 13.2.6Odor Cut Control, 13.3.3Overload Protection Control