INSTALL THE FLUE COLLECTOR

4.INSTALL THE FLUE COLLECTOR

1.Collect the Flue Collector cartons. The Flue Collector sections are labeled on the part and on the carton. See Table 4.1 for the items needed.

2.Install Hi Temp Rope for each collector section as shown in Figure 4.1. The rope provides the seal to prevent flue gases from leaking from the collector.

Make certain that the rope is well under the bottom edges of each flue collector section in order to obtain a tight seal.

3.Place the Flue Collector sections in the positions given in Table 4.1. These positions are numbered from left to right when facing the front of the boiler.

4.Fasten an angle bracket, part number GG-5005, to the top of each Collector section with two #10 x 1/2" (13 mm) long sheet metal screws. See Figure 4.2.

5.Insert a Long Hook Bolt, part number GG-5003,

through the angle bracket. Slip the hook end over

 

the tie rod. Apply a 1/4"-20 hex nut on the end of

 

the rod and snug against the bracket. See Figure 4.2.

Figure 4.2: Installing Flue Collector Sections

Do not tighten yet.

 

6. Insert a Short Hook Bolt, part number GG-5004,

 

through the flange in the rear of the flue collector.

 

Catch the hook around the spacer pads at the top of

 

the boiler sections. Apply a 1/4"-20 hex nut on the

 

Bolt and snug against the flange. See Figure 4.2. Do

 

not tighten yet.

 

7. Draw the Flue Collector sections tight against the

 

sealing rope by tightening the nuts on the Hook

 

Bolts. Draw the nuts evenly, alternating tightening.

 

Figure 4.1: Applying Flue Collector Hi Temp Rope Gasket

17