TROUBLESHOOTING – SERVICE TIPS

Problem

Possible Cause

Suggested Remedy

 

 

 

Main Gas Valve Opens

Manual Valve Closed at Gas Train

Open Valve

 

 

Manual Valve Closed at Meter

Open Valve

But No Gas Flows

 

 

Test Firing Valve Closed (if Provided)

Open Valve

 

 

 

 

 

Sags in Steam Piping or not enough Pitch

Correct Piping Condition

 

 

 

 

Concentric reducers causing condensate pooling

Correct Piping

 

 

 

Water Hammer On Start-Up

Drip trap failed closed

Replace Trap or Trap Element

 

 

Dry returns wetted due to new boiler water line

Correct Piping or Install Feed System and Traps

 

 

higher than old boiler

 

 

 

 

 

 

No drip line on the back side of a back-pitched

Install Drip Line and Trap

 

motorized valve

 

 

 

 

 

 

Clogged returns on gravity system

Clean or Re-Pipe Return Line(s)

 

 

 

 

Incorrect near-boiler piping causing wet steam

Correct Piping per Manual

 

to system

 

 

 

 

 

 

Trap failed open, allowing steam to enter returns

Replace Trap or Trap Element

 

 

 

 

{Radiator Hammer} Large radiator may be

Use smaller Air Vent or Use Two Small Vents in

 

Place of One Large Vent, One Mounted Higher

 

vented too quickly

 

than the Other

 

 

 

 

 

 

Long nipple at Hartford Loop

Replace with Close Nipple

 

 

 

Water Hammer During Mid-Cycle

Water leg or back slope in return line to receiver

Correct Piping

 

tank, causing water pocketing

 

 

 

 

 

 

Trap installed at receiver tank, causing water

Remove Trap at Tank, Installing Drip Traps and

 

trapping in return

Radiator Traps where Required

 

 

 

 

Boiler feed pump or condensate pump feed rate

Throttle Flow Rate

 

too fast, causing spraying into equalizer

 

 

 

 

 

 

No drip on the inlet side of a forward pitched

Add Drip Line and Trap

 

motorized valve

 

 

 

 

 

 

Uninsulated steam piping, causing excessive

Insulate Steam Pipes

 

condensate loads

 

 

 

 

 

 

Close nipple on Hartford too high

Repipe 2" to 4" (5cm to 10cm) Below Water Line

 

 

 

Water Hammer on Shut-Down

Uninsulated steam piping in boiler room, but

 

system piping insulated, causing vacuum

Insulate Steam Pipes

 

 

condition on shut-down

 

 

 

 

Hammering in the Boiler

Poor circulation in the boiler due to sludge

Clean and Blowdown the Boiler

accumulation

 

 

 

 

 

 

Main vents not working

Replace Main Vents, Repiping away from End

 

of Lines if Needed

 

 

 

 

 

 

Drip Traps failed closed

Replace Traps or Trap Elements

 

 

 

No Heat or Poor Heat Distribution

Radiator traps failed open, allowing pressurization

Replace Traps or Trap Elements

of the returns

in the Building

 

 

 

Water legs or back slope in return lines to receiver

Correct Piping

 

 

tank, preventing air from venting out receiver vent

 

 

 

 

 

 

Boiler pressure too high, causing air vents to lock

Reduce Operating Pressure

 

up or blowing water loop seals

 

 

 

 

 

 

New boiler water content smaller than old boiler

Install Boiler Feed System with Receiver Tank

 

Large enough for Condensate

 

 

 

 

 

 

Boiler water feed rate or pump rate too fast

 

System or Boiler Overfilling or Flooding

causing water level to collapse (due to collapse of

Reduce Feed Rate

 

steam bubbles in boiler water)

 

 

 

 

 

Foaming, priming or surging due to poor

Clean the Boiler

 

water quality

 

 

 

 

 

 

Poor water quality, causing foaming and surging

Clean the Boiler

 

 

 

Excessive Water Level Bounce

Incorrect near-boiler piping, such as undersized

Pipe per Manual

or incorrectly placed risers

 

 

 

 

 

 

Boiler water feed rate or pump rate too fast

Reduce Feed Rate

 

 

 

 

Air vents or traps not venting air, preventing

 

 

steam from getting to radiation and pressurizing

Replace Vents or Traps

Rapid Cycling

the air pocket

 

 

 

Pressure differential on pressure control too close

Adjust Control Differential

 

 

 

 

 

Nuisance outages of water level control due to

See Excessive Water Level Bounce Above

 

boiler water level bounce

 

 

 

 

 

47

Page 49
Image 49
PB Heat 211A manual Correct Piping