TROUBLESHOOTING – SERVICE TIPS
Problem | Possible Cause | Suggested Remedy | |
|
|
| |
Main Gas Valve Opens | Manual Valve Closed at Gas Train | Open Valve | |
|
| ||
Manual Valve Closed at Meter | Open Valve | ||
But No Gas Flows | |||
|
| ||
Test Firing Valve Closed (if Provided) | Open Valve | ||
| |||
|
|
| |
| Sags in Steam Piping or not enough Pitch | Correct Piping Condition | |
|
|
| |
| Concentric reducers causing condensate pooling | Correct Piping | |
|
|
| |
Water Hammer On | Drip trap failed closed | Replace Trap or Trap Element | |
|
| ||
Dry returns wetted due to new boiler water line | Correct Piping or Install Feed System and Traps | ||
| |||
| higher than old boiler | ||
|
| ||
|
|
| |
| No drip line on the back side of a | Install Drip Line and Trap | |
| motorized valve | ||
|
| ||
|
|
| |
| Clogged returns on gravity system | Clean or | |
|
|
| |
| Incorrect | Correct Piping per Manual | |
| to system | ||
|
| ||
|
|
| |
| Trap failed open, allowing steam to enter returns | Replace Trap or Trap Element | |
|
|
| |
| {Radiator Hammer} Large radiator may be | Use smaller Air Vent or Use Two Small Vents in | |
| Place of One Large Vent, One Mounted Higher | ||
| vented too quickly | ||
| than the Other | ||
|
| ||
|
|
| |
| Long nipple at Hartford Loop | Replace with Close Nipple | |
|
|
| |
Water Hammer During | Water leg or back slope in return line to receiver | Correct Piping | |
| tank, causing water pocketing | ||
|
| ||
|
|
| |
| Trap installed at receiver tank, causing water | Remove Trap at Tank, Installing Drip Traps and | |
| trapping in return | Radiator Traps where Required | |
|
|
| |
| Boiler feed pump or condensate pump feed rate | Throttle Flow Rate | |
| too fast, causing spraying into equalizer | ||
|
| ||
|
|
| |
| No drip on the inlet side of a forward pitched | Add Drip Line and Trap | |
| motorized valve | ||
|
| ||
|
|
| |
| Uninsulated steam piping, causing excessive | Insulate Steam Pipes | |
| condensate loads | ||
|
| ||
|
|
| |
| Close nipple on Hartford too high | Repipe 2" to 4" (5cm to 10cm) Below Water Line | |
|
|
| |
Water Hammer on | Uninsulated steam piping in boiler room, but |
| |
system piping insulated, causing vacuum | Insulate Steam Pipes | ||
| |||
| condition on |
| |
|
|
| |
Hammering in the Boiler | Poor circulation in the boiler due to sludge | Clean and Blowdown the Boiler | |
accumulation | |||
|
| ||
|
|
| |
| Main vents not working | Replace Main Vents, Repiping away from End | |
| of Lines if Needed | ||
|
| ||
|
|
| |
| Drip Traps failed closed | Replace Traps or Trap Elements | |
|
|
| |
No Heat or Poor Heat Distribution | Radiator traps failed open, allowing pressurization | Replace Traps or Trap Elements | |
of the returns | |||
in the Building |
| ||
|
| ||
Water legs or back slope in return lines to receiver | Correct Piping | ||
| |||
| tank, preventing air from venting out receiver vent | ||
|
| ||
|
|
| |
| Boiler pressure too high, causing air vents to lock | Reduce Operating Pressure | |
| up or blowing water loop seals | ||
|
| ||
|
|
| |
| New boiler water content smaller than old boiler | Install Boiler Feed System with Receiver Tank | |
| Large enough for Condensate | ||
|
| ||
|
|
| |
| Boiler water feed rate or pump rate too fast |
| |
System or Boiler Overfilling or Flooding | causing water level to collapse (due to collapse of | Reduce Feed Rate | |
| steam bubbles in boiler water) |
| |
|
|
| |
| Foaming, priming or surging due to poor | Clean the Boiler | |
| water quality | ||
|
| ||
|
|
| |
| Poor water quality, causing foaming and surging | Clean the Boiler | |
|
|
| |
Excessive Water Level Bounce | Incorrect | Pipe per Manual | |
or incorrectly placed risers | |||
|
| ||
|
|
| |
| Boiler water feed rate or pump rate too fast | Reduce Feed Rate | |
|
|
| |
| Air vents or traps not venting air, preventing |
| |
| steam from getting to radiation and pressurizing | Replace Vents or Traps | |
Rapid Cycling | the air pocket |
| |
|
| ||
Pressure differential on pressure control too close | Adjust Control Differential | ||
| |||
|
|
| |
| Nuisance outages of water level control due to | See Excessive Water Level Bounce Above | |
| boiler water level bounce | ||
|
| ||
|
|
|
47