![Remote Emergency Power-off Installation](/images/new-backgrounds/131871/13187155x1.webp)
INSTALLATION
7.Plug the UPS power cord into an
The μindicator flashes, indicating the UPS is in Standby mode with the equipment offline.
8.Press the On
button (see Figure 14 on page 31).
The μindicator illuminates solid and the bar graph indicators display the percentage of load being applied to the UPS. The UPS is now in Normal mode and supplying power to your equipment.
The UPS automatically sets the output voltage based on the input voltage. To change the output voltage, see “Configuration” on page 35.
NOTE The batteries charge to 80% capacity in less than 2 hours. However, it is recommended that the batteries charge for 24 hours after installation or
NOTE If you installed power management software and optional EBMs, ensure maximum battery runtime by using the Virtual Front Panel UPS utility on the Software Suite CD.
Remote Emergency Power-off Installation
The Powerware 9125 includes a REPO connector that allows power to be switched off at the UPS output from a
The REPO feature shuts down the protected equipment immediately and does not follow the orderly shutdown procedure initiated by any power management software.
Any devices that are operating on battery power are also shut down immediately. When the REPO switch is reset, the equipment will not return to battery power until the UPS is manually restarted.
If the Off button is pressed after the REPO is activated, the UPS remains in Standby mode when restarted until the On button is pressed.
22EATON Powerware® 9125