Powerware 6000 VA, 5000 manual Weights and Dimensions, Battery Runtimes in Minutes

Models: 6000 VA 5000

1 66
Download 66 pages 55.12 Kb
Page 55
Image 55

SPECIFICATIONS

Table 8. Weights and Dimensions

 

UPS

Extended Battery Module (EBM)

 

 

 

Dimensions

44.2 x 68.3 x 21.8 cm

44.2 x 68.3 x 13 cm

(WxDxH)

17.4” x 26.9” x 8.6” (5U)

17.4” x 26.9” x 5.1” (3U)

Weights

UPS Chassis: 35 kg (77 lb)

69.9 kg (154 lb)

 

Internal Battery Trays (2): 27.4 kg (60.5 lb) each

 

 

Total UPS Weight: 89.8 kg (198 lb)

 

 

 

 

Table 9. Battery

Configuration

(20) 12V, 7.2 Ah internal batteries

EBM Configuration

PW9125 240 EBM: (20) 12V, 9 Ah

 

 

Type

Sealed, maintenance-free, valve-regulated, lead-acid

Charging

Internal battery: less than 2 hours to 80% usable capacity at nominal line voltage after

 

full load discharge

 

External battery: no more than 15x discharge time to 90% usable capacity at nominal

 

line voltage after full load discharge

 

 

Monitoring

Advanced monitoring for earlier failure detection and warning

 

 

Table 10. Battery Runtimes (in Minutes)

Load

UPS Internal

1 EBM

2 EBMs

3 EBMs

4 EBMs

Batteries

 

 

 

 

 

 

 

 

 

 

 

6000 VA/4200W

9.7

29.7

52.1

76.3

102

 

 

 

 

 

 

5000 VA/3500W

13.2

37.4

65.3

95.6

127.7

 

 

 

 

 

 

4000 VA/2800W

19.2

49.2

85.8

125.4

167.5

 

 

 

 

 

 

3000 VA/2100W

24.3

70.1

121.9

178.0

237.4

 

 

 

 

 

 

2000 VA/1400W

37.7

107.5

186.2

271.4

361.6

 

 

 

 

 

 

NOTE Battery times are approximate and vary depending on the load configuration and battery charge.

EATON Powerware® 9125 Two-in-One UPS (5000/6000 VA) User’s Guide S 164201513 Rev B

49

www.powerware.com

 

Page 55
Image 55
Powerware 6000 VA, 5000 manual Weights and Dimensions, Battery Runtimes in Minutes, Extended Battery Module EBM