CONFIGURATION
3Press the Test/Alarm Reset button ONCE to select the
option.
Test/Alarm
Reset Button
Bar Graph Indicators
1 & 4
Press and hold the On and Test/Alarm Reset buttons simultaneously for three
seconds to toggle between Configuration and Operation modes.
On Button
2Press the On button to scroll to the next option.
Figure 17. Using Configuration Mode
Table 2. Configuration Mode LEDs and Options
Bar Graph Indicators | Option | LED Status | Explanation |
| 240V Nominal Output | On | Nominal output voltage is 240V. |
| Voltage |
| All other nominal output voltages are disabled. |
|
| Flashing | 240V is disabled; one of the other output voltage |
|
|
| options is selected. |
| 230V Nominal Output | On | Nominal output voltage is 230V. |
| Voltage |
| All other nominal output voltages are disabled. |
|
| Flashing | 230V is disabled; one of the other output voltage |
|
|
| options is selected. |
| 220V Nominal Output | On | Nominal output voltage is 220V. |
| Voltage |
| All other nominal output voltages are disabled. |
|
| Flashing | 220V is disabled; one of the other output voltage |
|
|
| options is selected. |
| 208V Nominal Output | On | Nominal output voltage is 208V. |
| Voltage |
| All other nominal output voltages are disabled. |
|
| Flashing | 208V is disabled; one of the other output voltage |
|
|
| options is selected. |
| Site Wiring Fault | On | Alarm sounds when the polarity of the outlet is |
| Alarm |
| reversed or the ground connection is missing; have a |
|
|
| qualified electrician repair the outlet wiring. |
|
| Flashing | Alarm DOES NOT sound when the polarity of the outlet |
|
| (default) | is reversed or the ground connection is missing. |
36EATON Powerware® 9125