Turning the UPS Off

OPERATION

Turning the UPS Off

NOTE Pressing the Off Initiating the Battery Test button while the UPS is in Battery mode causes the UPS to shut down immediately.

To turn off the UPS:

1.Prepare your equipment for shutdown.

2.Press and hold the Off Manual background button for approximately three seconds. The μindicator begins to flash. The UPS switches to Standby mode (if utility power is available) and removes power from your equipment.

3.Unplug or remove utility power from the UPS; the UPS shuts down in five seconds. The bar graph and battery indicators flash briefly prior to shutdown.

If you do not unplug or remove utility power from the UPS, it remains in Standby mode.

Initiating the Battery Test

NOTE The batteries must be fully charged and the UPS must not be in Battery mode to perform the battery test.

NOTE For an accurate battery test, test the UPS with at least 50% load applied to the UPS.

The UPS automatically performs a battery test every 30 days. If the UPS switches to Battery mode, the UPS resets the timer.

To initiate a battery test, press and hold the Manual background button for three seconds. The UPS cycles the bar graph indicators twice, verifies the battery converter, and schedules the battery test to occur within 24 hours.