Testing New Batteries

UPS MAINTENANCE

5.Slide the new battery trays into the chassis.

6.Reinstall the battery retaining bracket.

7.Replace the lower UPS front cover.

Testing New Batteries

NOTE The batteries must be fully charged and the UPS must not be in Battery mode to perform the battery test.

NOTE For an accurate battery test, test the UPS with at least 50% load applied to the UPS.

To test the new batteries:

1.Plug the UPS into a power outlet (apply utility power on hardwired models) for 24 hours to charge the battery.

2.After charging the battery, press and hold the Manual background button for three seconds to initiate a battery test.

The UPS cycles the bar graph indicators twice, verifies the battery converter, and schedules the battery test to occur within 24 hours.