SPECIFICATIONS

Table 6. Electrical Output

Regulation

Nominal output voltage ±3%

(Normal Mode)

 

Regulation

Nominal output voltage ±3%

(Battery Mode)

 

Voltage Waveform

Normal mode: Sine wave; <3% THD with linear or PFC load;

 

<6% with nonlinear load or SMPS

Output Receptacles

L6-30R or Hardwired

 

 

Table 7. Environmental and Safety

Operating Temperature

0°C to 40°C (32°F to 104°F)

 

Optimal battery performance: 25°C (77°F)

Storage Temperature

0°C to 25°C (32°F to 77°F)

Transit Temperature

-25°C to 55°C (-13°F to 131°F)

Relative Humidity

5–95% noncondensing

Operating Altitude

Up to 3,000 meters above sea level

Transit Altitude

Up to 10,000 meters above sea level

Heat Dissipation

2066 BTU/hr maximum

Audible Noise

Less than 50 dBA Normal mode, typical load

 

Less than 60 dBA Battery mode

Leakage Current

< 0.6 mA

Communication

DB-9: 1200-19200 baud; USB 1.1 compliant

Surge Suppression

ANSI C62.41 Category B3

 

EN 61000-4-5 Level 3, Criteria B

Safety Conformance

UL 1778;

 

CSA C22.2, No. 107.1, 107.2;

 

EN 50091-1-1 and IEC 60950;

 

NOM-019-SCFI

 

 

Agency Markings

cULus, cUL, NOM-NYCE, CE

 

UL/DEMKO GS (hardwired models only)

EMC (Class A)

EN 50091-2, FCC Part 15, ICES-003

 

 