Figure 12. Hardwired UPS Rear Panel

INSTALLATION

To hardwire the UPS:

1.If you are installing power management software, connect your computer to the USB port or UPS communication port (see page 37). For the communication port, use only the serial cable supplied in the accessory kit.

2.Switch off utility power at the distribution point where the UPS will be connected. Be absolutely sure there is no power.

3.Remove the wiring access cover and the conduit landing plate and retain (see Figure 12).

Punch holes in the conduit landing plate for the input and output conduit using a Greenlee® punch or similar device.

USB Port Communication Port

X-Slot Communication

Bay

Manual background REPO Connector

Manual background Battery Connector

Battery Circuit

Breaker

Conduit Landing Plate

Wiring Access Cover

Figure 12. Hardwired UPS Rear Panel

4.Pull the input and output wires through separate conduit, leaving approximately 0.5m (2 ft) of exposed wire. Attach a flexible metal fitting to the end of each conduit.

5.Insert each conduit through a wiring access entry and attach the conduit fitting to the panel. Strip 1.5 cm (0.5I) of insulation from the end of each incoming wire.