R
December 6, 2011 7051-158B Page 41
EDGE 60 Pellet Fireplace
E. Chimney and Exhaust Connection
1. Chimney & Connector: Use 3 or 4 inch (76-102mm)
diameter type "L" or "PL" venting system. It can be vented
vertically or horizontally.
2. Mobile Home: Approved for all Listed pellet vent. As
with all installations a Quadra-Fire Outside Air Kit must
be used with manufactured home installations.
3. INSTALL VENT AT CLEARANCES SPECIFIED BY THE
VENT MANUFACTURER.
4. Exhaust Venting System: Secure to the appliance with
at least 2 screws 180 degrees apart. Also secure all
connector pipe joints with at least 3 screws through each
joint.
NOTE: All pipe must be welded seam pipe whenever
possible. Seal pipe joints with high temperature silicone
(500°F [260°C] minimum rated only).
NOTE: If burning shelled fi eld corn, you must use
approved venting specifi cally designed for corn. Follow
the instructions from the venting manufacturer.
Only LISTED venting components may be used.
NO OTHER vent components may be used.
• Substitute or damaged vent components may impair
safe operation.
WARNING! RISK OF FIRE!
WARNING! RISK OF INJURY OR PROPERTY
DAMAGE!
Improper installation, adjustment, alteration, service or
maintenance can cause injury or property damage.
Refer to the owner ’s information manual provided with this
appliance.
For assistance or additional information consult a qualifi ed
installer, service agency or your dealer.
The table below can help you calculate the equivalent feet
of pipe which is a method used to determine pellet vent size.
Figure 40.1.
F. Equivalent Feet of Pipe
Figure 40.1
2 ft.
2 ft.
3 ft.
2 ft.
Example of 3 Elbow-Rear Vent Termination Calculation
Pellet Venting
Component
# of
Elbows
Feet of
Pipe
Multiplied
By
Equivalent
Feet
Components
Equivalent Feet
90o Elbow or Tee 3X515
45o Elbow X3
Horizontal Pipe 7X 17
Vertical Pipe 2X 0.5 1
Total Equivalent Feet 23
Note: This is a generic example and is not
intended to represent any specifi c fuel type.
Vent surfaces get HOT, can cause burns
if touched. Non-combustible shielding or
guards may be required.
WARNING
CAUTION!
DO NOT CONNECT THIS UNIT TO A CHIMNEY
FLUE SERVING ANOTHER APPLIANCE.
DO NOT INSTALL A FLUE DAMPER IN THE EX-
HAUST VENTING SYSTEM OF THIS UNIT.