Regency G36D UltraGlow DIRECT VENT SYSTEM FLEX, Propane & Natural Gas, Installation

Models: G36D

1 44
Download 44 pages 31.34 Kb
Page 14
Image 14
UltraGlow® DIRECT VENT SYSTEM (FLEX)

INSTALLATION

RIGID PIPE VENTING ARRANGEMENTS - HORIZONTAL TERMINATIONS

UltraGlow® DIRECT VENT SYSTEM (FLEX)

(Propane & Natural Gas)

The diagram shows all allowable combinations of vertical runs with horizontal terminations, using one 90o elbow (two 45o elbows equal one 90o elbow).

Note: Must use optional rigid pipe adaptor (Part # 510-994) when using rigid vent systems.

All Rigid Pipe Systems

4" inner diameter

6-5/8" outer diameter

UltraGlow® Flex Vent 4" inner diameter

6-7/8" inner diameter

A vent guard should be used whenever the termination is lower than the specifi ed minimum or as per local codes.

Note: UltraGlow® Direct Vent System (Flex) is only approved for horizontal terminations.

Maintain clearances to combustibles as listed in the "Clearances," "Mantel Leg Clearances," "Framing and Finishing," & "Combustible Mantels" sections.

Horizontal vent must be supported every 3 feet.

Firestops are required at each floor level and whenever passing through a wall.

14

UltraGlow® G36D Zero Clearance Direct Vent Gas Fireplace

Page 14
Image 14
Regency G36D UltraGlow DIRECT VENT SYSTEM FLEX, Propane & Natural Gas, Installation, 6-5/8outer diameter