Regency G36D Installation, Propane & Natural Gas, Vent must be supported at offsets

Models: G36D

1 44
Download 44 pages 31.34 Kb
Page 16
Image 16
•Vent must be supported at offsets

INSTALLATION

RIGID PIPE VENTING ARRANGEMENTS - VERTICAL TERMINATIONS

(Propane & Natural Gas)

The G36D is approved for a maximum 23 ft. (7.0m) vertical, with a maximum 12 ft. (3.7m) horizontal offset using two 90o elbows (two 45o elbows equal one 90o elbow) with Rigid Pipe vent systems for Propane and Natural Gas, as per diagram 1.

The G36D is approved for a maximum 37 ft. (11.3m) straight vertical, including a maximum 20" (0.5m) horizontal offset using two 90o elbow (two 45o elbows equal one 90o elbow) with Rigid Pipe vent systems for Propane and Natural Gas, as per diagram 2.

Vent must be supported at offsets

Maintain clearances as listed in the"Clearances" section.

Firestops are required at each floor level and whenever passing through a wall.

Note: Must use optional rigid pipe adaptor when using rigid vent systems (Part # 510-994).

Note: UltraGlow® Direct Vent System (Flex) is only approved for horizontal terminations.

Diagram 1

Diagram 2

16

UltraGlow® G36D Zero Clearance Direct Vent Gas Fireplace

Page 16
Image 16
Regency G36D installation manual Installation, Propane & Natural Gas, Vent must be supported at offsets