Regency L676 Installation, Vertical Venting with Two 2 90o Elbows, Option, V H + H1 V +

Models: L676

1 56
Download 56 pages 33.98 Kb
Page 21
Image 21
Vertical Venting with Two (2) 90o Elbows

INSTALLATION

Vertical Venting with Two (2) 90o Elbows

INSTALLATION

One 90o elbow = Two 45o elbows.

Option V

H

V + V1 With these options, max. total pipe

A)2' Min. 2' Max. 3' Min. length is 30 feet with min. of 6 feet total vertical and max. 8 feet total

B)2' Min. 10' Max. 6' Min. horizontal.

C)3' Min. 6' Max. 4' Min.

D)4' Min. 7' Max. 5' Min. Please note min. 1 foot between

E)5' Min. 8' Max. 6' Min. 90o elbows is required.

VENT RESTRICTOR SETTING:

Vent restrictor must be at Set 0 for both NG and LP.

Vertical Venting with Three (3) 90o Elbows

One 90o elbow = Two 45o elbows.

Option

V H + H1 V + V1

A)2' Min. 2' Max. 4' Min.

B)3' Min. 4' Max. 6' Min.

C)4' Min. 5' Max. 7' Min.

D)5' Min. 6' Max. 8' Min.

E)6' Min. 8' Max. 9' Min.

With these options, max. total pipe length is 30 feet with min. of 9 feet total vertical and max. 8 feet total horizontal.

Please note min. 1 foot between 90o elbows is required.

VENT RESTRICTOR SETTING:

Vent restrictor must be at Set 0 for both NG and LP.

Regency® L676 Direct Vent Gas Fireplace

21

Page 21
Image 21
Regency L676 Installation, Vertical Venting with Two 2 90o Elbows, Vertical Venting with Three 3 90o Elbows, Option