INSTALLATION
Vertical Venting with Two (2) 90o Elbows
INSTALLATION
One 90o elbow = Two 45o elbows.
Option V | H | V + V1 With these options, max. total pipe |
A)2' Min. 2' Max. 3' Min. length is 30 feet with min. of 6 feet total vertical and max. 8 feet total
B)2' Min. 10' Max. 6' Min. horizontal.
C)3' Min. 6' Max. 4' Min.
D)4' Min. 7' Max. 5' Min. Please note min. 1 foot between
E)5' Min. 8' Max. 6' Min. 90o elbows is required.
VENT RESTRICTOR SETTING:
Vent restrictor must be at Set 0 for both NG and LP.
Vertical Venting with Three (3) 90o Elbows
One 90o elbow = Two 45o elbows.
Option | V H + H1 V + V1 |
A)2' Min. 2' Max. 4' Min.
B)3' Min. 4' Max. 6' Min.
C)4' Min. 5' Max. 7' Min.
D)5' Min. 6' Max. 8' Min.
E)6' Min. 8' Max. 9' Min.
With these options, max. total pipe length is 30 feet with min. of 9 feet total vertical and max. 8 feet total horizontal.
Please note min. 1 foot between 90o elbows is required.
VENT RESTRICTOR SETTING:
Vent restrictor must be at Set 0 for both NG and LP.
Regency® L676 Direct Vent Gas Fireplace | 21 |