INSTALLATION
INSTALLATION
Horizontal Venting with Two (2) 90o Elbows
H1
V
One 90o elbow = Two 45o elbows.
Option |
| V |
| H + H1 | W i t h t h e s e o p t i o n s, |
| |
A) | 2' | Min. |
| 4' Max. |
| ||
| maximum total pipe length |
| |||||
B) | 3' | Min. |
| 6' Max. |
| ||
| is 30 feet with minimum |
| |||||
|
|
|
|
|
|
| |
C) | 4' | Min. |
| 8' Max. | of 6 feet total vertical and |
| |
D) | 5' | Min. |
|
|
| maximum 10 feet total |
|
| 9' Max9'Max. |
| |||||
|
|
|
|
|
| horizontal. |
|
E) | 6' Min. | 10' Max. |
| ||||
|
| ||||||
|
|
|
|
|
|
|
|
Please note minimum 1 foot between 90o elbows is required.
VENT RESTRICTOR SETTING:
Vent restrictor factory set at Set 1, no adjustment required.
Horizontal Venting with Three (3) 90o Elbows
H1
V1
One 90o elbow = Two 45o elbows.
H
V
Option V | H | V + V1 H + H1 |
A)2' Min. 1' Max. 3' Min. 2' Max.
B)2' Min. 2' Max. 5' Min. 4' Max.
C)3' Min. 2' Max. 7' Min. 5' Max.
D)4' Min. 3 Max. 9' Min. 6' Max.
E)5' Min. 4' Max. 10' Min. 7' Max.
F)6' Min. 6' Max. 11' Min. 9' Max.
With these options, max. total pipe length is 30 feet with min. of 11 feet total vertical and max. 9 feet total horizontal.
Please note min. 1 foot between 90o elbows is required.
VENT RESTRICTOR SETTING:
Vent restrictor factory set at Set 1, no adjustment required.
22 | Regency® L676S Direct Vent Gas Fireplace |