Regency L676S-NG1 Pilot Adjustment, High Elevation, Gas Line Installation, over tighten

Models: L676S-NG1

1 48
Download 48 pages 49.23 Kb
Page 28
Image 28
L676S-NG1 SYSTEM DATA

INSTALLATION

INSTALLATION

 

 

L676S-NG1 SYSTEM DATA

Note: To properly check gas pressure, both

 

inlet and manifold pressures should

Min. Supply Pressure

5" WC (1.25 kpa)

 

be checked using the valve pressure

Low Setting Man.

1.6" WC (0.39 kpa)

 

ports on the valve.

 

 

Pressure

 

1) Make sure the valve is in the "OFF"

Max. Manifold

3.5" WC (0.87 kpa)

 

position.

Pressure

 

2) Loosen the "IN" and/or "OUT" pressure tap(s),

Orifice Size

#37 DMS

 

turning counterclockwise with a

Minimum Input

19,500 Btu/h

 

 

1/8" wide flat screwdriver.

 

(5.71 kW)

 

 

Maximum Input

29,000 Btu/h

3)

Attach manometer to "IN" and/or "OUT"

 

pressure tap(s) using a 5/16" ID hose.

 

(8.49 kW)

 

L676S-LP1 SYSTEM DATA

4)

Light the pilot and turn the valve to "ON"

Min. Supply Pressure

12" WC (2.98 kpa)

 

position.

 

 

Low Setting Man.

6.4" WC (1.59 kpa)

5)

The pressure check should be carried out

Pressure

 

 

with the unit burning and the setting should

Max. Manifold

10" WC (2.49 kpa)

 

be within the limits specified on the safety

Pressure

 

 

label.

Orifice Size

#53 DMS

6) When finished reading manometer, turn off the

Minimum Input

21,000 Btu/h

PILOT ADJUSTMENT

gas valve, disconnect the hose and tighten the

 

(6.15 kW)

 

screw (clockwise) with a 1/8" flat screwdriver.

Maxiumm Input

26,000 Btu/h

 

Note: Screw should be snug, but do not

 

over tighten.

 

(7.61 kW)

 

 

 

 

HIGH ELEVATION

This unit is approved in Canada for altitude 0 to 4500 ft. (CAN1 2.17-M91).

GAS LINE

INSTALLATION

Since some municipalities have additional local codes it is always best to consult with your local authorities and the CAN/CGA B149 installation code.

For USA installations follow local codes and/ or the current National Fuel Gas Code, ANSI Z223.1.

When using copper or flex connectors use only approved fittings. Always provide a union so that gas lines can be easily disconnected for servicing. Flare nuts for copper lines and flex connectors are usually considered to meet this requirement.

IMPORTANT: Always check for gas leaks with a soap and water solution or gas leak detector. Do not use open flame for leak testing.

Periodically check the pilot flames. Correct flame pattern has three strong blue flames: 1 flowing around the thermopile, 1 around the thermocouple and 1 flowing across the burner (it does not have to be touching the burner).

Note: If you have an incorrect flame pattern, contact your Regency® dealer for further instructions.

Incorrect flame pattern will have small, probably yellow flames, not coming into proper contact with the rear burner or thermopile or thermocouple.

GAS PIPE PRESSURE

TESTING

The appliance must be isolated from the gas supply piping system by closing its individual manual shut-off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig. (3.45 kPa). Disconnect piping from valve at pressures over 1/2 psig.

The manifold pressure is controlled by a regulator built into the gas control, and should be checked at the pressure test point.

SIT 820 VALVE DESCRIPTION

1)Gas on/off knob

2)Manual High/Low Adjustment

3)Pilot Adjustment

4)Thermocouple Connection - option

5)Outlet Pressure Tap

6)Inlet Pressure Tap

7)Pilot Outlet

8)Main Gas Outlet

9)Alternative TC Connection Point

28

Regency® L676S Direct Vent Gas Fireplace

Page 28
Image 28
Regency L676S-NG1 Pilot Adjustment, High Elevation, Gas Line Installation, Gas Pipe Pressure Testing, over tighten