INSTALLATION
Vertical Venting with Three (3) 90o Elbows
One 90o elbow = Two 45o elbows.
Option | V H + H1 V + V1 With these options, max. total |
A)2' Min. 2' Max. 4' Min. pipe length is 30 feet with min. of 9 feet total vertical and max.
B)3' Min. 4' Max. 6' Min. 8 feet total horizontal.
C)4' Min. 5' Max. 7' Min.
D)5' Min. 6' Max. 8' Min. Please note min. 1 foot
E)6' Min. 8' Max. 9' Min. between 90o elbows is required.
VENT RESTRICTOR SETTING:
Vent restrictor factory set at Set 1, no adjustment required.
V1
H1 | H | V |
|
|
INSTALLATION
Regency® L676S Direct Vent Gas Fireplace | 23 |