Regency P40-NG, P40-LP Unit Assembly Prior To Installation, Venting Introduction, Screw

Models: P40 P40-LP P40-NG

1 48
Download 48 pages 12.68 Kb
Page 12
Image 12
UNIT ASSEMBLY

INSTALLATION

INSTALLATION

UNIT ASSEMBLY

PRIOR TO

INSTALLATION

NOTE:TheTopFacingSupport,theSideNailing Strips and the 2 Top Standoffs must be correctly positioned and attached before unit is slipped into position.

TOP STANDOFF ASSEMBLY

The top standoffs are shipped in a fl at position and must be folded into shape and attached.

1)Remove the standoffs from top of the fi replace.

2)Take each standoff and bend into the correct shape. Bend up at the bend lines until the screw holes in the standoff and the pre- punched screw holes on the fi replace top line up.

3)Attach the standoff securely to the top with 2 screws per standoff (on opposite corners).

TOP FACING SUPPORT AND

SIDE NAILING STRIPS

Determine the total thickness of facing material to allow the fi nished surface to be fl ush with the front of the unit. Total facing thickness can vary from 1/2" (13mm) to 1-1/4" (32mm) thick.

TheTopFacingSupport&SideNailingStripscan be mounted in 3 different positions depending on the thickness of the facing material.

Screw

Facing Material Depth

Position

 

A1/2" / 13mm

B7/8" / 22mm

C*

1-1/4" / 32mm

*For "C" screw position the top facing support is reversed.

1)Mount Top Facing Support using the 3 supplied screws into the three pre-punched screw holes on the top front of the unit. Use hole positions A, B, or C depending on your facing depth.

Note: For screw position C with a facing material depth of 1-1/4" (32mm), the top facing support must be reversed.

2)Use the same screw hole position for the Side Nailing Strips as was used for the Top Facing Support. Attach each side nailing strip using 3 screws.

Note: When installing side strips into position C, the side strips are not reserved.

VENTING

INTRODUCTION

The P40 uses the "balanced fl ue" technology Co Axial system. The inner liner vents products of combustion to the outside while the outer liner draws outside combustion air into the combustion chamber thereby eliminating the need to use heated room air for combustion and losing warm room air up the chimney.

Note: These flue pipes must not be connected to any other appliance.

The gas appliance and vent system must be vented directly to the outside of the building, and never be attached to a chimney serving a separate solid fuel or gas burning appliance.

Each direct vent gas appliance must use it's own separate vent system. Common vent systems are prohibited.

VENT RESTRICTOR

POSITION

Vent restriction is required for certain venting installations, see the diagrams in the "Venting Arrangements" section to determine if they are required for your installation.

To set the Vent restriction as indicated in the diagrams in the "VentingArrangements" section, refer to the instructions below;

1)Remove the top louver if installed.

2)Loosen the screw on the vent restrictor indicating plate.

3)Rotate the vent restrictor adjustment rod counter clockwise to line up the slot on the indicating plate with the point on the air box to the required setting.

4)Tighten screw to lock position.

VENTINGScrew

Point on AirBox

Factory Set Vent Restrictor Setting

(no adjustment required)

Point on AirBox

Vent Restrictor setting at Set 1

Point on AirBox

Vent Restrictor setting at Set 2

12

Regency® P40 Direct Vent Gas Fireplace

Page 12
Image 12
Regency P40-NG, P40-LP Unit Assembly Prior To Installation, Venting Introduction, Vent Restrictor Position, Screw